Use and Care Manual

15
EN
e use of a fault current protection switch is not mandatory. If a fault current protection switch is used, only AC/DC
sensitive RCD protective devices (type B or B+) are permitted.
11.3. Fault current protection switch
Even when the device is switched off, voltage is applied to terminals and connections. Do not touch the device
for 5 minutes after all-pole disconnection from the mains.
12. COMMISSIONING
Commissioning by trained technical personnel may only be performed after any risk has been ruled out. e
following checks should be performed in accordance with the installation and operating manual and the regu-
lations in force:
Correctly sealed installation of the unit and duct system.
Check the duct system, unit and medium lines, if present, remove any foreign bodies if necessary.
e intake opening and inflow into the unit must be clear.
Check all mechanical and electrical protection measures (e.g. earthing).
Voltage, frequency and type of current must correspond with the rating plate.
Servicing, troubleshooting and cleaning may only be performed by specialised personnel in accordance
with this installation and operating manual and the regulations in force.
Make sure that no connections or components are loosened unless the device is disconnected from
the mains. Make sure that the equipment cannot be switched back on again.
Individual components must not be interchanged. For example, the components intended for one pro-
duct may not be used for other products.
e regular maintenance and care of our devices is designed to ensure proper function, value retention
and avoidance of damage. Keep a maintenance log.
Perform the specified maintenance on the unit at the specified intervals.
13. MAINTENANCE AND CLEANING
During operation, electric motors heat up. Under certain circumstances (excessively high ambient or fluid temperatu-
res, heavy contamination, etc.), the motor temperature may exceed the safety limit of the electrically isolated parts.
In order to avoid engine damage, various types of temperature monitoring are possible, of which at least one must be
installed on site. (Exception: fans with thermal contacts integrated in the motor current)
Applies for versions with led out thermal contact: No warranty in case of a not connected ermal Contact. Damages
caused by overheating will not be considered.
11.2. ermal motor protection
www.ruck.eu |