1.4 Configure the DIP Switches
1.4.1 Setting the Protocol that is required on site.
Selecting the required Protocol
To configure the Protonode to match what is on site please follow the below chart
identifying the dipswitch settings for the different configurations. For example, if the
BMS requires communication over Bacnet IP and there are four boilers on site the
technician would select Bacnet IP 4 Sola and configure the S0 – S3 dipswitches on the
ProtoCarrier accordingly.
Power must be cycled after the dip switch settings have been adjusted in order for the
changes to take effect