Installation guide

Page 25 of 51
1 = On
CH Enable
00D0
0208
AV
/AO
48
R/W
0 = Disable Central Heating
1 = Enable Central Heating
CH Setpoint
00D3
0211
AV
/AO
49
48
R/W
-
40
130
o
C (0.1
o
C precision)
1
CH Time of
Day Setpoint
00D4
0212
AV
/AO
50
49
R/W
-
40
130
o
C (0.1
o
C precision)
1
.
Reserved for future use
CH Outdoor
Reset Enable
00D7
0215
AV
/AO
51
50
R/W
0 = Disable outdoor reset
1 = Enable outdoor reset
Prepurge
Time
00E7
0231
AV
/AO
52
R/W
SAFETY PARAMETER
0-64800 seconds (18 hours)
Postpurge
Time
0
0EC
0236
AV
/AO
53
R/W
SAFETY PARAMETER
0-64800 seconds (18 hours)
DHW
Demand
Switch
01C1
0449
AV
/AO
54
53
R/W
0 = DHW Disabled
1 = DHW Enabled
DHW
Setpoint
01C5
0453
AV
/AO
55
54
R/W
-
40
130
o
C (0.1
o
C precision)
1
Outlet High
Limit
Setpoint
01D0
0464
AV
/AO
56
R/W
SAFETY PARAMETER
-40 – 130
o
C (0.1
o
C precision)
1
CH Outdoor
Max Outdoor
Temperature
0200
0512
AV
/AO
58
57
R/W
-
40
130
o
C (0.1
o
C precision)
1
CH Outdoor
Min Water
Temperature
0201
0513
AV
/AO
59
58
R/W
-
40
130
o
C (0.1
o
C precision)
1
CH Frost
Protection
Enable
0210
0528
AV
/AO
60
R/W
0 = Disable
1 = Enable