11 = System pump demand
10 = Boiler pump demand
9 = DHW pump demand
8 = CH pump demand
Reason
7 = Reserved
6 = Pump assigned to logical pump
5 = Pump exercise requested
4 = Pump on due to exercise
3 = Pump on due to Post pump
2 = Forced off
1 = Forced on
0 = On due to normal demand
Outdoor
Temperature
00AA
0170
AI
/AI
41
40
R
-
40
–
130
o
C (0.1
o
C precision)
1
Operating
System (OS)
Number
00BA
0186
AI
/AI
42
R
Variable length string (up to 16
characters)
Date Code
00BB
0187
AI
/AI
43
R
Variable length string (up to 10
characters)
Safety
processor
build
00BC
0188
AI
/AI
44
R
Application
processor
build
00BD
0189
AI
/AI
45
R
Installer
Password
00BE
0190
AV
/AO
46
45
W
Password: sola
Burner
Switch
00CB
0203
AV
/AO
47
46
R/W
Used to enab
le/disable burner control
0 = Off