Installation guide

Page 22 of 51
Pump A
Status
005D
0093
AI
/AI
32
31
R
Bitmap
15 – 14 = Reserved
13 = Auxiliary 2 pump demand
12 = Auxiliary 1 pump demand
11 = System pump demand
10 = Boiler pump demand
9 = DHW pump demand
8 = CH pump demand
Reason
7 = Reserved
6 = Pump assigned to logical pump
5 = Pump exercise requested
4 = Pump on due to exercise
3 = Pump on due to Post pump
2 = Forced off
1 = Forced on
0 = On due to normal demand
Pump B
Status
005E
009
4
AI
/AI
33
32
R
CH pump
status
0060
0096
AI
/AI
34
33
R
Application Build < 1600
Application Build > 1600
DHW pump
status
0064
0100
AI
/AI
35
34
R
System
pump status
0069
0105
AI
/AI
36
35
R
Boiler Pump
Status
006C
0108
AI
/AI
37
36
R
Burner Cycle
Count
0080
-
0081
0128
-
0129
AV
/AO
89
R/W
0
-
999,999
Burner Run
Time
0082
-
0083
0130
-
0131
AV
/AO
90
R/W
0
-
999,999 hours
CH Pump
0084
-
0085
0132
-
0133
AV
/AO
91
3
R/W
0
-
999,999