1.10 Connect to the ProtoNode using RUI (Ruinet)
- Double click on the debugging utility, “RUINET” (Remote User Interface). The
following screen will appear: (if Ruinet does not automatically display the main
menu, select the ProtoNode by typing the 2-digit number to the left of the title
name).
Figure 7: RUINET screen
- Select “O” for Connection Overview to see the number of messages on each
protocol. If the ProtoNode is communicating correctly with the device then the
display will show Tx and Rx messages without any errors.
- If there are errors on the ProtoNode socket communications, edit the points list
in the CSV file until there are no errors. Each time the points the points are
edited, the CSV will need to be re-downloaded using Ruinet.
- When communication between the device and the ProtoNode is established the
Field Side of the ProtoNode may be connected to the appropriate
device/software. Ensure that the Field Side parameters on the device/software
are setup as per the “ProtoNode Mapping” document.
- Read and write data from each side and make sure the ProtoNode works as
expected.