Data Sheet
Camtec Power Supplies GmbH – Gewerbestraße 30 – DE76327 Pfinztal – Germany
p.2/5 (06.2016-02-2)
Phone +49(0)721 46596-0 - Fax +49(0)721 46596-77 – www.camtec-gmbh.com - info@camtec-gmbh.com
(Subject to alterations. This product is not designed to be used in applications such as life support systems wherein a failure or malfunction could result in injury or death)
Technical Table
Model
ESB101.05UPS ESB101.16 ESB101.23 ESB101.23S ESB101.33 ESB101.LED.230VAC
ESB101.LED.115VAC ESB101.23S.115VAC
Peak Current
Limiting ±6%
5A
16A
23A
23A
33A
48A
43A
23A
R.M.S Current
Limiting ±6%
3,5A
11,3A
16,3A
16,3A
23,3A
33,9A
30,4A
16,3A
Maximum A
llowed
Capacitive Load
1.000uF
1.500µF
2.000uF
2.000uF
4.000µF
6.000uF
10.000uF
4.000µF
Limiting Time
(T
on
Power On)
900
ms
(±50ms)
3
00
ms
(±50ms)
300
ms
(±50ms)
5
00
ms
(±50ms)
3
00
ms
(±50ms)
3
00
ms
(±50ms)
300
ms
(±50ms)
500
ms
(±60ms)
Release Time
(T
off
Low Voltage)
1400
ms
(±50ms)
500
ms
(±50ms)
5
00
ms
(±50ms)
800
ms
(±80ms)
500
ms
(±50ms)
550
ms
(±50ms)
550
ms
(±50ms)
900
ms
(±80ms)
Limiting Interval
[T
interval
for AC
cont.
)
≥ 900ms
≥ 900ms
≥ 900ms
≥ 1400ms
≥ 900ms
≥ 900ms
≥ 900ms
≥ 1400ms
Quickest advisable
Circuit breaker at
30°C
A2A
A6A
B4A
Z6A
A10A
B6A
Z10A
A10A
B6A
Z10A
A13A
B8A
Z13A
B13A
A16A
B13A
Z16A
A10A
B6A
Z10A
AC
Input Range
184
-
265Vac
90
-
130Vac
AC
Continuous
Input Range
230Vac
115Vac
Line Frequency
16
⅓ Hz
–
440Hz
16
⅓ Hz
–
440Hz
Switch
-
On Voltage
144Vac
79Vac
AC Lower Margin
52
Vac
(
AC dump / drop
out voltage
)
28Vac
(AC dump / drop
out voltage
)
AC
Current
16A
contin
u
ous
load current
Power Supply
No external power supply required,
item is self
-
power
ing
Current
Consumption
19mA
constant at contin
u
ous operation
(2,2W @ 115Vac / 4,4W @ 230Vac)
Limiting
Cycles
B
etween each limiting action shall be a break of
20 sec.
, to let the device cool down until the next limiting starts
Intern
al Protection
Thermal fuse protects
from
over
heat
& fire
Cooling
Natural convection
Operation
Temp.
Ambient temperature
-
40°C ... +6
0
°C
cont
inuous
(see operations temperature list for details in this manual)
Storage Temp.
-
40°C
...
+85°C
for 2 years
EMI
EN55022
class
B
EMS
EN61000
-
6
-
2,3
Safety Norms
EN60950
-
1
, several units: ANSI/UL508 &
CAN/CSA C22.2 (see product list for details in this manual)
, UL
-
File: E485106
Safety Class
II
VDE0805, VDE0100
/
ÖVE8001
ROHS conformity
ROHS Directive 2011/65/EU
REACH conformity
REACH Directive 1907/2006
MTBF
Calculation
30
0
.
000h
(IEC
/EN61709, Siemens
SN29500)
MTTF
Calculation
384.000h (+30°C)
(IEC/EN61709, Siemens SN29500)
Humidity
95%
(+25
°C)
not condensing
Pollution Degree
2 (IEC/EN50178)
Environmental
T
hermal environment
3K3
,
mechanics
3M4 (IEC/EN60721)
Altitude max.
4
000m
(13123 ft.)
above sea level
Dimension
s
(WxHxD)
(
Wide=
2TE)
,
36,5
x
110
x
62mm
Ho
using
Parameters
UL94V
-
0 (E45329), ABS/NH6020,
RTI 110°C, housing for DIN/VDE0603
cutout box
and for wall mount
DIN
-
Rail
DIN
-
Rail
TS35mm DIN/EN60715 (TS35/7,5 und TS35/15)
Weight
12
1
g
/ 0,27 lb
Connections
Spring
-
type terminal with
cable protection
0,5...6mm²
21
…10
AWG
according with
IEC/EN60664
-
1, IEC/EN61984
Use copper conductors only. Tightening torque per terminal block is 0.5 - 0.6 Nm / 4.5 - 5.3 lbf-in