Specifications

SDM-SIO1 Serial Input/Output Module
There can be up to 15 SDM-SIO1s on a single SDM bus. Each SDM-SIO1 will
need to have a unique address before they are powered up. If other equipment
is present on the bus, whether it’s an SDM-SIO1 or not, the user needs to
insure no addresses are the same.
TABLE 3-1. SDM Address Settings
Rotary Switch
Position
SDM Address
SerialOpen Command
Comm. Port Number
0 0 32
1 1 33
2 2 34
3 3 35
4 4 36
5 5 37
6 6 38
7 7 39
8 8 40
9 9 41
A 10 42
B 11 43
C 12 44
D 13 45
E 14 46
F
(1)
15
(1)
47
(1)
(1) Address ‘F’ is not available as it’s the broadcast address. Setting this
address will result in the SDM-SIO1 having an address of ‘0’ not ‘F’.
3.1 Connections
Connection to the SDM-SIO1 is achieved via the 15 terminals arranged along
the top of the unit. The terminals are spring loaded providing an easy and
reliable method of connection. Wires should be stripped .25” (7mm), twisted
and inserted in the round hole while opening the clamp by pushing a
screwdriver in the adjacent rectangular hole, or by pushing a screwdriver into
the hole on the side of the connector. Remove the screwdriver to close the
clamp making sure the clamp grips the wire rather than the plastic insulation.
If there is a need to insert more than one wire in a terminal when using
multistrand wire, twist the conductors together first. If using solid wires, either
solder or crimp wires together before insertion. For RS-485 connections note
that the RS-232 terminals double up as a secondary connection, so it is rare to
have multiple conductors in one terminal as both sets of connections can be
used either for forming an RS-485 daisy-chain or for adding termination
resistors at each end of a network.
6