Specifications
Section 4. Maintenance, Troubleshooting, and Schematics
TABLE 4.2-2. Gill WindSonic Diagnostic Codes
Diagnostic Status Comment
0 Okay All okay
1 Axis 1 Failed Insufficient samples, possible path obstruction
2 Axis 2 Failed Insufficient samples, possible path obstruction
4 Both Axis Failed Insufficient samples, possible path obstruction
8 NVM error Nonvolatile Memory checksum failed
9 ROM error Read Only Memory checksum failed
10 Maximum Gain Questionable wind measurements
4.3 Schematics of Connectors
Knowledge of schematics is not necessary for routine installation and
maintenance. Each connector has a small molded dot by pin 1. All of the
schematics show the pinned connectors on the cables. Socketed connectors on
the back of the enclosure are the mirror images of what’s shown.
4-11