reconnecting the battery plug. Keypad should power up and
the message “HELLO” seen on the display.
Call Campbell Scientific if still no response.
No Response from Datalogger through SC32A or Modem
Peripheral
At the datalogger:
Make sure the battery has been installed and the power
switch set to “ON” (section 4.1.1 – 4.1.3).
Use a voltmeter to measure the voltage on the 12V and G
terminals (see Figure 17); the voltage must be between 9.6
and 16 VDC.
Use a voltmeter to measure the voltage on the 5V and G
terminals (see Figure 17); the voltage must be between 4.9 –
5.1 VDC.
Make sure the datalogger is connected to the
communication peripheral, and the communication
peripheral properly installed and configured (section 3.3).
At the computer:
Make sure calling software is properly configured (PC200W,
VisualWeather, or LoggerNet).
Check the cable(s) between the serial port and the modem.
If cables have not been purchased through Campbell
Scientific, check for the following configuration using an ohm
meter:
25-pin serial port:
computer end modem end
2 2
3 3
7 7
20 20
9-pin serial port:
computer end modem end
2 3
3 2
4 20
5 7
Make sure the communication device at the computer is
properly configured and cabled (section 3.3).
Call Campbell Scientific if still no response.
-99999 Displayed in an Input Location