Specifications
RavenXTG Sierra Wireless Cellular Modem
Light Patterns
The LEDs on the front of the modem will respond in different patterns to
indicate modem states.
• Normal—Each LED, mentioned above, lit as applicable.
• Start up—The LEDs will cycle from left to right.
• PassThru mode—Network and Signal LEDs will blink in tandem. The
Activity LED will blink when transmitting or receiving data.
• SOS—The Network LED blinks.
• Configuration Reset—The LEDs will cycle left to right and then right to
left 4 times.
• Authentication Failure—The Network, Signal, and Activity LEDs blink
every 2 seconds.
• Data Retry—The Network, Signal, and Activity LEDs blink every 3
seconds.
6. LoggerNet/PC400 Software Setup
The Device Map is configured from the “Setup” button on the
LoggerNet/PC400 Toolbar. Configure the Device Map as described below.
1. Select Add Root | IPPort.
2. Add a datalogger to the IPPort (PakBus dataloggers, e.g. the CR1000,
require a PakBusPort).
3. On the IPPort page, add the IP address and the Port number (the Raven
template file configures the port to be 3001). Add four seconds of extra
response time.
4. For PakBus dataloggers, leave the default settings on the PakBusPort
page.
5. For PakBus dataloggers, set the PakBus address to match that of the
datalogger (default address in the datalogger is 1). Make sure that
“PakBus Always Open” is unchecked.
15