Appendix A. AceManager Setup without Template File
A-2
x S23 – Configure Serial Port – The baud rate needs to be configured to
match a valid datalogger baud rate. For a CR10X: 9600,8N1 and for a
CR1000: 115200,8N1.
x \Q – Serial Port Flow Control – This should be set to None.
x V – AT Verbose Mode – Set this to Verbose for CR800, CR1000,
CR3000; Numeric for CR10(X), CR510, CR23X.
x &D – DTR Mode – Set to Ignore DTR
x S211 – DTR Mode – Set to Ignore DTR
x &S – Assert DSR – Set to In Data Mode
x &C – Assert DCD – Set to In Data Mode
x Q – Quiet Mode – Set to ON