Product manual

NL200 Network Link Interface
7. Operation
This section describes how to configure your NL200 for different operational
modes. See Section 4 for help in determining which mode to use.
7.1 Bridge Mode
7.1.1 Physical Set-up
Power the NL200 through the barrel connector jack located on the edge of the
device. Connect the NL200 to your local network using an Ethernet cable,
attaching one end to the NL200's Ethernet port and the other end to your
network. Connect the supplied SC12 serial cable from the NL200’s CS I/O
port to the datalogger’s CS I/O port.
7.1.2 Configuring the NL200
Connect to the NL200 in DevConfig (see Section 6). In the NL200 tab, set
Bridge Mode to ‘enable’.
7.1.3 Configuring the Datalogger
Connect a serial cable from the PC COM port to the datalogger’s RS-232
port.
Open DevConfig. Select the device type of the datalogger (CR800,
CR1000, or CR3000), the appropriate Communication Port and baud rate.
Press the “Connect” button to connect to the datalogger.
Under CS I/O Interface on the TCP/IP tab, input the IP Address, Subnet
Mask and IP gateway. These values can be provided by your network
administrator. If using DHCP, the address will automatically be displayed.
Press the “Apply” button to save the changes and then close DevConfig.
The NL200 must be connected to the datalogger before
configuring the datalogger with DevConfig. If it is not
connected, the TCP/IP settings will not be displayed.
NOTE
7.1.4 LoggerNet Set-up
The next step is to run LoggerNet and configure it to connect to the datalogger
via the Ethernet port. (See example in Figure 7-1 below.)
In LoggerNet’s Setup Screen press Add Root and choose IPPort. Input the
datalogger’s IP address and port number. The IP address and port number
are input on the same line separated by a colon. (The datalogger’s default
port number is 6785. It can be changed using DevConfig or by modifying
its value in the Status Table. Unless firewall issues exist, the port number
does not need to be changed from its default value.)
Add a PakBus Port.
Add the datalogger (CR800, CR1000, or CR3000) and input the PakBus
address of the datalogger.
11