Product manual
Section 1. NL115 Ethernet/CompactFlash
®
Module Overview
Campbell Scientific's NL115 Ethernet/CompactFlash
®
Module provides two independent
capabilities: (1) enables 10baseT Ethernet communications and (2) stores data on a
removable CompactFlash card. It allows the datalogger to communicate over a local
network or a dedicated Internet connection via TCP/IP. It also expands on-site data
storage and provides the user with a convenient method of transporting data from the field
back to the office. This small, rugged communication device connects to the 40-pin
peripheral port on a CR1000 or CR3000 datalogger.
This section of the manual surveys the NL115 and its functions. It also explains how to
quickly begin using an NL115 for straightforward Ethernet communications and data
storage operations. The remainder of the manual is a technical reference which describes
in detail such operations as: TCP/IP functionality, file formats, datalogger programming
and data retrieval.
1.1 Specifications
Storage Capacity: Depends on card size (up to 2 GB supported)
Power Requirements: 12 V supplied through datalogger’s peripheral
port
Current Drain: 20 mA (CR1000 w/NL115 communicating
over Ethernet)
43 mA (CR1000 w/NL115 communicating
over Ethernet and accessing CF-card)
Operating Temp. Range: -25°C to +50°C Standard
-40°C to +85°C Extended
EMI and ESD Protection: Meets requirements for a class A device under
European Standards
Application of Council Directive(s):
89/336/EEC as amended by 89/336/EEC and
93/68/EEC
Standards to which conformity is declared:
EN55022-1; 1995 and EN50082-1: 1992
Cable Requirements: Ethernet cable must be shielded if the length is
greater than 9 ft.
Typical Access Speed: 200 - 400 Kb/sec
Memory Configuration: User selectable for either ring style (default) or
fill and stop.
1-1