Specifications
Met One 034B Windset 
TABLE 5-1. Wind Speed Multiplier* 
Model  Meters/Second  Miles/Hour 
034B 
M = 0.7989 
Off = 0.28 
M = 1.787 
Off = 0.63 
*When configured to output counts, the multiplier above is divided 
by the execution interval in seconds. 
5.2 Wind Direction 
The CR200(X) dataloggers use the ExDelSE instruction to measure wind 
direction. All other CRBasic dataloggers (e.g., CR800, CR1000, CR3000, 
CR5000) use the BRHalf instruction (see Section 5.4.1 for example). 
Edlog dataloggers (CR510, CR10(X), CR23X) typically use Instruction 5 – 
AC Half Bridge (P5) to measure wind speed (see Section 5.4.2 for example). 
When the sensor cable length is greater than 100 ft, Edlog Instruction 4 – 
Excite-Delay (P4) is recommended instead (see Section 5.5). 
Excitation voltages, range codes, and multipliers for our dataloggers are listed 
in Table 5-2. The multiplier value converts the sensor’s millivolt output to 
degrees. Appendix B has additional information on the measurement 
instructions. 
TABLE 5-2. Parameters for Wind Direction 
CR10(X) 
CR510 
CR7 
21X 
CR23X 
CR800 
CR1000 
CR5000 
CR3000 
CR200(X) 
Measurement Range, 
Integration 
2500 mV, slow  5000 mV, 
slow/60 Hz 
2500 mV, 
60 Hz, reverse 
excitation 
5000 mV, 
60 Hz, reverse 
excitation 
N/A 
Excitation Voltage  2500 mV  5000 mV  2500 mV  5000 mV  2500 mV 
Multiplier 720* 720* 720  720  0.288 
Offset 0 0 0 0 0 
*The multiplier for the Edlog dataloggers assumes Edlog Instruction 5 – AC Half Bridge is used. Refer to Section 
5.5 if using Edlog Instruction 4 – Excite-Delay. 
5.3 Wind Vector Processing Instruction 
The Wind Vector output instruction is used to process and store mean wind 
speed, unit vector mean wind direction, and Standard Deviation of the wind 
direction (optional) from the measured wind speed and direction values. 
6 










