Operator`s manual
51
Manual
4: Do (P86)
  1: 41      Set Port 1 High
;CONTROL PORT1 IS CONNECTED WITH A JUMPER TO SW12CTRL
;(SWITCHED 12 VOLT CONTROL)
5: Excitation with Delay (P22)
  1: 3       Ex Channel
  2: 0       Delay W/Ex (units = 0.01 sec)
  3: 10      Delay After Ex (units = 0.01 sec)
  4: 0       mV Excitation
;DELAY OF 0.1 SEC TO ALLOW CS500 TO WARM UP AND STABILIZE
;INSTRUCTION (P22) ONLY SERVES FOR DELAYING THE PROGRAM
;NO ACTUAL EXITATION IS NEEDED. E3 IS NOT WIRED
6: Volt (SE) (P1)
  1: 1       Reps
  2: 5       2500 mV Slow Range
  3: 1       SE Channel
  4: 1       Loc [ AIR_TEMP  ]
  5: 0.1      Mult
  6: -40      Offset
;TEMPERATURE MEASUREMENT WITH CS500 SENSOR, CONNECTED TO SINGLE
;ENDED CHANNEL 1. TEMPERATURE MEASURED IN DEGREES CELSIUS.
7: Volt (SE) (P1)
  1: 1       Reps
  2: 5       2500 mV Slow Range
  3: 2       SE Channel
  4: 2       Loc [ RH       ]
  5: 0.1      Mult
  6: 0.0      Offset
;RELATIVE HUMIDITY MEASUREMENT WITH CS500 SENSOR, CONNECTED TO
;SINGLE ENDED CHANNEL 2. RH MEASURED IN PERCENTAGE.
8: Do (P86)
  1: 51      Set Port 1 Low
;SWITCH OFF CS500
9: Volt (Diff) (P2)
  1: 1       Reps
  2: 2       7.5 mV Slow Range
  3: 2       DIFF Channel
  4: 3       Loc [ SOLAR_RAD ]
  5: 200      Mult
  6: 0.0      Offset
;INCOMMING SOLAR RADIATION MEASUREMENT WITH LI200X SENSOR, CONNECTED
;TO DIFFERENTIAL CHANNEL 2.
;THE OUTPUT FROM LI200X IS 0.2 kW/M2, mV. MAXIMUM INCOMING SHORTWAVE SOLAR
Annexes