Instruction manual

28
connection for PPP communications requires the use of a null modem cable to
connect the datalogger RS-232 to the modem ‘Data’ port.
5.3.8.1 IPn3Gb COM1 PPP Configuration
It is necessary to configure COM1 to use PPP so that the datalogger can
communicate with a network using a PPP connection. Other PPP settings can
be adjusted as needed, but any changes must be reflected appropriately in the
modem and datalogger configuration.
x Under COM1, navigate to the ‘Config’ tab
x Data Baud Rate = 115200
x Character Timeout = 50
x Protocol config = select ‘PPP’
x
Expected String = delete ‘CLIENT’ and leave field blank
x
Response String = ‘CONNECT’ (Entry must be all upper case)
x
PPP Local IP = 192.168.0.1 (This is the default local IP of the
modem)
x
PPP Host IP = 192.168.0.99 (This is the IP address that will be
assigned to the datalogger)
x
Submit (Save)
The following parameters need to be setup the same in both the modem and
datalogger:
x Baud rate
x Data format
x Handshaking