Instruction manual
13
(e.g. FTP client, Email client, HTTP server, and FTP server). For information
on the PPP configuration procedure, see Section 5.3.8. However, a TCP server
configuration is also possible for use with these dataloggers if IP functionality
is not required.
For any datalogger without an IP stack (e.g. CR200X series or legacy
dataloggers), a TCP server configuration is the only option.
The settings below are applicable to the TCP server configuration. Parameters
which are not specified below, should be left at the default settings.
Under COM1 navigate to the ‘Config’ tab.
x Data Baud Rate = 115200 for use with a CR800 series, CR1000, or
CR3000 datalogger (or 9600 for use with a CR200X series or legacy
datalogger)
x Character Timeout = 50
x No-Connection Data Intake = Disable
x Protocol config = TCP server
x Local listening port = 6785 (default datalogger PakBus/TCP Service
port)
In order to avoid confusion or unwanted communication, it is recommended to
change this port to match the last 4 digits of the modem’s cellular telephone
number. This must be done in the modem (COM1 & Firewall), the datalogger,
and LoggerNet.
x Submit (Save)
NOTE