Specifications

Appendix A. CR3000 Status Table
A-7
accessing an array with a variable index such as arr(index) = arr(index-1),
where index is a variable).
8 The self calibration is run automatically in a slow scan (Section 3.8.)
9 The order of tables is the order in which they are declared.
10 Card bytes free is shown = -1 when no card is present.
11 displays large number until a SlowScan runs.
12 MaxSlowProcTime displays 0 until a SlowScan runs.
13 Security can be changed via DeviceConfig, CR3000KD, PBGraph,
StatusTable, and SetSecurity instruction. Shows -1 if security code has
not been given/deactivated.
14 When the SerialOpen instruction is used CommsConfig is loaded with the
format parameter of that instruction. Currently (11/2004), the only
formatting option available is 0 = No error checking. PakBus
communication can occur concurrently on the same port If the port was
previously opened (in the case of the CP UARTS) for PakBus, or if the
port is always opened ( CS-9pin, and RS232) for PakBus the code will be
4.
15 The value show is the initial baud rate the CR3000 will use. A negative
value will allow the CR3000 to auto baud but will dictate at which baud
rate to begin
16 A list of up to 8 PB addresses for routers that can act as Central Routers.
See DeviceConfig for more information.
17 (1) 5000 mV range 250 uS integration,
(2) 2500 mV range 250 uS integration,
(3) 250 mV range 250 uS integration,
(4) 25 mV range 250 uS integration,
(5) 7.5 mV range 250 uS integration,
(6) 2.5 mV range 250 uS integration,
(7) 5000 mV range 1/60 Hz integration,
(8) 2500 mV range 1/60 Hz integration,
(9) 250 mV range 1/60 Hz integration,
(10) 25 mV range 1/60 Hz integration,
(11) 7.5 mV range 1/60 Hz integration,
(12) 2.5 mV range 1/60 Hz integration,
(13) 5000 mV range 1/50 Hz integration,
(14) 2500 mV range 1/50 Hz integration,
(15) 250 mV range 1/50 Hz integration,
(16) 25 mV range 1/50 Hz integration,
(17) 7.5 mV range 1/50 Hz integration,
(18) 2.5 mV range 1/50 Hz integration