Operator`s manual
SECTION 8. PROCESSING AND PROGRAM CONTROL EXAMPLES
8-10
* 1 Table 1 Programs
01: 1 Sec. Execution Interval
01: P17 Panel Temperature
01: 16 Loc [:PANL TEMP]
02: P1 Volt (SE)
01: 6 Reps
02: 5 5000 mV slow Range
03: 1 IN Chan
04: 1 Loc [:W1 ]
05: .018 Mult
06: 0 Offset
03: P14 Thermocouple Temp (DIFF)
01: 4 Reps
02: 11 5 mV fast Range
03: 7 IN Chan
04: 2 Type E (Chromel-Constantan)
05: 16 Ref Temp Loc PANL TEMP
06: 7 Loc [:Ta2 ]
07: 1 Mult
08: 0 Offset
04: P37 Z=X*F
01: 1 X Loc W1
02: 1.2222 F
03: 1 Z Loc [:W1 ]
05: P37 Z=X*F
01: 4 X Loc W2
02: 1.2222 F
03: 4 Z Loc [:W2 ]
06: P54 Block Move
01: 5 No. of Values
02: 4 First Source Loc W2
03: 1 Source Step
04: 11 First Destination Loc [:W2 ]
05: 1 Destination Step
07: P31 Z=X
01: 9 X Loc Ta1
02: 4 Z Loc [:W2 ]
08: P57 Wet/Dry Bulb Temp to VP
01: 17 Pressure Loc
02: 9 Dry Bulb Temp Loc Ta1
03: 10 Wet Bulb Temp Loc Tw1
04: 5 Loc [:U2 ]
09: P57 Wet/Dry Bulb Temp to VP
01: 17 Pressure Loc
02: 14 Dry Bulb Temp Loc Ta2
03: 15 Wet Bulb Temp Loc Tw2
04: 15 Loc [:Tw2 ]
10: P92 If time is
01: 0 minutes into a
02: 30 minute interval
03: 10 Set high Flag 0 (output)
11: P62 CV/CR (OSX-0)
01: 5 No. of Input Values
02: 5 No. of Means
03: 5 No. of Variances
04: 0 No. of Std. Dev.
05: 4 No. of Covariances
06: 2 No. of Correlations
07: 300 Samples per Average
08: 1 First Sample Loc W1
09: 20 Loc [:MEAN (W1)]
12: P62 CV/CR (OSX-0)
01: 5 No. of Input Values
02: 5 No. of Means
03: 5 No. of Variances
04: 0 No. of Std. Dev.
05: 4 No. of Covariances
06: 2 No. of Correlations
07: 300 Samples per Average
08: 11 First Sample Loc W2
09: 36 Loc [:MEAN (W2)]
13: P77 Real Time
01: 110 Day,Hour-Minute
14: P70 Sample
01: 35 Reps
02: 20 Loc MEAN (W1)
15: P End Table 1
* A Mode 10 Memory Allocation
01: 54 Input Locations
02: 79 Intermediate Locations