Operator`s manual

15 SERIAL INPUT
6
01: P 15 Serial Input
01: 1 Repetitions
02: 1 Diff Input Chnl
03: 1 Dig Ctrl Prt X=TTL/1X=RS232
04: 9 Number Characters/Input
05: 83 Delay (1=0.012 sec)
06: 1 Input Loc
07: 1 Multiplier
08: 0 Offset
02: P 89 If X<=>F START: Limit testing
01: 1 X Loc AIR mb
02: 3 >=
03: 1300 F
04: 11 Set high Flag 1 then set Flag 1 high
03: P 89 If X<=>F
01: 1 X Loc AIR mb
02: 4 < If reading is < 800 mb
03: 800 F
04: 30 Then Do then set Flag 1
04: P 91 If Flag If Flag 1 is set,
01: 11 1 is set
02: 30 Then Do do the following.
05: P 86 Do Output time of failure
01: 10 Set high Flag 0 (output)
06: P 77 Real Time
01: 110 Day,Hour-Minute
07: P 70 Sample Output out of range reading
01: 1 Rep
02: 1 Loc AIR mb
08: P 86 Do Set Intermediate Processing
01: 19 Set high Flag 9 Disable Flag
09: P 86 Do Set Flag 1 low
01: 21 Set low Flag 1
10: P 95 End End of Flag Then Do
11: P 92 If time is Output mb twice/day
01: 0 minutes into a
02: 770 minute interval
03: 10 Set high Flag 0 (output)
12: P 77 Real Time
01: 110 Day,Hour-Minute
13: P 71 Average
01: 1 Rep
02: 1 Loc AIR mb