Specifications
Appendix B. Status Table
B-8
Status Fieldname Description Variable
Type
Default Normal
Range
User can
change?
Info
Type
pppDial Specifies the dial string that follows
ATD (e.g., #777 for Redwing CDMA)
or a list of AT commands separated by
';' (e.g., ATV1;
AT+CGATT=0;ATD*99***1#), that
will be used to initialise and dial
through a modem before a PPP
connection is attempted. A blank string
means that dialling is not necessary
before a PPP connection is established.
String _
pppDialResponse Specifies the response expected after
dialing a modem before a PPP
connection can be established.
String connect _ Yes
Messages Contains a string of messages that can
be entered by the user.
String _ Yes
CalGain
18
Calibration table of Gain values. Each
integration / range combination has a
gain associated with it. These numbers
are updated by the background slow
sequence if needed in the program.
Float
array of
18
_ . _ Calib
CalSeOffSet
18
Calibration table of single ended offset
values. Each integration / range
combination has a single ended offset
associated with it. These numbers are
updated by the background slow
sequence if needed in the program.
Integer
array of
18
_ close to 0 _ Calib
CalDiffOffset
18
Calibration table of differential offset
values. Each integration / range
combination has a differential offset
associated with it. These numbers are
updated by the background slow
sequence if needed in the program.
Integer
array of
18
_ close to 0 _ Calib
1
The StationName instruction can also be used in a program to write to this
field.
2
Pak Bus Addresses 1 to 4094 are valid. Addresses >= 4000 are generally
used for a PC by PC200, PC400, or LoggerNet.
3
Watchdog errors are automatically reset upon compiling a new program.
4
Replace the lithium battery if <2.7V. See section 1.10.2 for replacement
directions.
5
The 12V low comparator has some variation, but typically triggers at
about 9.0 volts. The minimum specified input voltage of 9.6 V will not
cause a 12 V low, but a 12 V low condition will stop the program
execution before the CR1000 will give bad measurements due to low of
supply voltage.
6
Currently not being used (12/1/2004)