Specifications
Section 8. CR1000 Configuration
8-4
The information in the dialog helps to corroborate the signature of the
operating system sent.
8.2.2 Sending OS to Remote CR1000
Operating systems can be sent remotely using the Program Send feature in
LoggerNet, PC400, and PC200W. Sending an OS via Program Send retains
settings unless changes in the new OS prevent it. To ensure a remote OS
download does not alter telecommunications settings, a program named
default.cr1 can be sent prior to the OS being sent.
Assuming default.cr1 is a small program loading a minimum of settings, after
sending the OS, default.cr1 runs automatically and sets all pertinent settings to
ensure continued communications with the base PC. Default.CR1 will also
ensure that a non-compiling CRBASIC program does not lock out a remote
user.
Depending on the method and quality of
telecommunications, sending an OS via Program Send
may take an inordinate amount of time.
8.2.3 Sending OS Using CF Card
Refer to Section 12.6 File Control.
8.3 Settings via DevConfig
The CR1000 has a number of properties, referred to as “settings”, some of
which are specific to the PakBus communications protocol.
Read more! PakBus is discussed in Section 14 PakBus Overview and the
PakBus Networking Guide available at www.campbellsci.com.
DevConfig | Settings Editor tab provides access to most of the PakBus settings,
however, the Deployment tab makes configuring most of these settings easier.
CAUTION