Instruction manual

Section 3. Radiotelemetry Network Components
3-2
RF310M
FIGURE 3-1. The RF310M Modem
TABLE 3-1. A Sample of Station ID Numbers and
the Corresponding Switch Settings
Station Switch Settings
ID 1234 56789
0 0000 0000X
10 0101 0000X
20 0010 1000X
30 0111 1000X
40 0001 0100X
50 0100 1100X
60 0011 1100X
70 0110 0010X
80 0000 1010X
90 0101 1010X
100 0010 0110X
110 0111 0110X
120 0001 1110X
130 0100 0001X
*Station ID 255 is reserved for phone-to-RF base stations.
The RF310M is shipped with the switch set for the RF310M-ME state and
station ID of 1.
3.1.3 Setting Station ID
Each RF310M, including the one in the RF base station, must have a unique
Station ID. The station ID is similar to a phone number. This allows one base
station to communicate with any one particular field station.
The Station ID can be any number from 1 to 255. The Station ID is set with the
switch inside the RF310M. The first eight dip switches are used to set the
Station ID. Table 3-1 shows the switch settings for several Station ID numbers.
Appendix A shows all possible Station ID numbers. The dip switches can