User manual
User Manual 
17 
Table 7-1. Wiring Diagram 
Colour 
Description 
CR800, 
CR850, 
CR1000, 
CR3000, 
CR10(X), 
CR510, CR500 
CR23X 
CR5000 
CR200(X) 
White  SDI-12 Signal  Odd Numbered 
Control Port 
(C1, C3…) 
Odd Numbered 
Control Port 
(C1, C3…) 
Odd Numbered 
Control Port 
(C1, C3…) 
SDI-12 C1/SDI-12 
Clear Chassis Ground 
G 
Red +12V (Power 
Supply for 
Sensor) 
12V 12V 12V  12V Battery+ 
Black Ground   G  G 
G G 
7.4.2  Multiple Sensors Connection 
To use more than one probe per datalogger, you can either connect the different 
probes to different SDI-12 compatible ports on the datalogger or change the SDI-12 
addresses of the probes and let them share the same connection. Using the SDI-12 
address minimizes the use of ports on the datalogger and also allows probes to be 
connected in a daisy-chain fashion which can minimize cable runs in some 
applications. 
7.4.3  Built-in Self Test (BIST) 
After connecting the sensor to the datalogger’s power terminals, the sensor performs 
a BIST (built-in self test) for approximately 80 seconds (factory default). During 
this self-check, an internal check of the electronics occurs. 
7.5 Programming 
This section is for users who write their own datalogger programs. A 
datalogger program to measure this sensor can be created using 
Campbell Scientific’s Short Cut Program Builder software. These 
sensors are not listed in the sensor list in Short Cut. Instead, select 
SDI-12 sensor under General Measurements (see Section 4.4, Step 4 
— Use SCWin Short Cut to Program Datalogger and Generate 
Wiring Diagram, for more information about using Short Cut). You 
do not need to read this section to use Short Cut. 
The radar sensor’s output is measured using a standard SDI-12 instruction to read 
the data from an SDI-12 sensor. If using the sensor with other SDI-12 recorders, 
please refer to your system’s documentation. Further details of the SDI-12 
commands can be found in Appendix B and at: www.sdi-12.org. 
7.5.1 CRBasic 
Dataloggers that are programmed with CRBasic include the CR200(X) series, 
CR800, CR850, CR1000, CR3000, and CR5000. These dataloggers use the 
SDI12Recorder() instruction to read the sensor. The SDI12Recorder() instruction 
should only be ran in the sequential mode. 
NOTE