CS215 Temperature and Relative Humidity Probe
6.3 CR200 Series Datalogger
1. Connect a single CS215 to the datalogger using Control Port C1/SDI12 as
described in Section 4, and download a datalogger program that does not
contain the SDI12Recorder () instruction.
2. In the LoggerNet Toolbar, navigate to and activate the Test|Terminal
Emulator … menu. The “Terminal Emulator” window will open. In the Select
Device menu, located in the lower left hand side of the window, select the
station.
3. Click on the Open Terminal button. If communications between the
datalogger and PC are successful, the red bar located in the upper left hand
side of the window, will turn green.
4. Press the <enter> key until the datalogger responds with the “
CR200>
prompt.
5. To query the CS215 for its current SDI-12 address, press the <enter> key, at
the “
CR200>” prompt, make sure you are in Caps Lock mode and enter the
command SDI-12>?! and press the <enter> key. The CS215 will respond
with the SDI-12 address.
6. To change the SDI-12 address, press the <enter> key. At the “
CR200>
prompt enter the command
SDI12>aAb! Where a is the current address
(shown in the above step) and b is the new address. The CS215 will change
its address and the datalogger will exit the SDI-12 Transparent Mode and
respond with “
Fail”.
7. Verify the new SDI-12 address. Press the <enter> key, at the “
CR200>
prompt enter the command SDI12>?! and press the <enter> key. The CS215
will respond with the new address.
FIGURE 3. Screen Capture of SDI-12 Transparent Mode on CRBasic CR200 Series Datalogger using
Control Port C1/SDI12 and Changing SDI-12 Address from 0 to 1