Specifications
Section 7. Measurement Instructions 
7-14 
Parameter 
& Data Type 
Enter 
CAOChan 
The CAO channel to set. 
Constant 
Alpha Numeric Description   
CAO1  1  CAO channel 1 
CAO2  2  CAO channel 2 
CAOmV 
Constant or 
Variable
The voltage, in millivolts, to apply to the CAO Channel. The allowable range is ±5000 
mV. The voltage can be constant or a variable can be used to vary the analog output in 
response to time or measurements.
Boost 
Sets the current that the CAO can sink (The CAO can always source up to 15 mA.) 
Constant 
Alpha Code  Value  Result   
False  0  Boost off: Maximum current sink 5 mA 
True 
≠0 
Boost Enabled: Maximum current sink 15 mA 
FastUpdate 
Shortens the execution time of the instruction and the settling time for the excitation. 
Alpha Code  Value  Result   
False  0  Settle 10 time constants (~2.6 ms) 
True 
≠0  Settle 1 time constant (~300 µs) 
ExciteI (IxChan, IxuA, XDelay) 
This instruction sets the specified current excitation channel to the current 
specified. 
Parameter 
& Data Type 
Enter 
IxChan 
Enter the current excitation channel number to use to excite the first measurement. 
Constant 
Alpha 
Code 
Code/ 
Channel 
Result       
IX1  1  Current Excitation Channels (IxChan) 
IX2 2           
IX3 3           
IX4 4           
ExuA 
Constant 
The excitation current in microamps.  The allowable range is ±2500 µA.  
XDelay 
Specifies the length of time the current channel is enabled, after which, the channel is set 
low and the datalogger moves on to the next instruction. If XDelay is set to 0, the 
excitation will be on until the end of the program scan or until another instruction sets an 
excitation voltage, CAO, or current channel.
ExciteV (ExChan, ExmV, XDelay) 
This instruction sets the specified switched voltage excitation channel to the 
voltage specified. The XDelay parameter is used to specify the length of time 
the excitation channel is enabled, after which, the channel is set low and the 
datalogger moves on to the next instruction. If the SettlingTime is set to 0, the 
excitation channel will be enabled and the voltage will be held until the end of 
the program scan or until another instruction sets an excitation voltage, CAO, 
or current channel. 