Instruction manual

9522B Iridium Satellite Modem and COM9522B Interface Modem
5.1.5 Step 5: PakBusPort Configuration
As shown in FIGURE 5-5, select the PakBusPort. Be sure the
Communications Enabled box is checked, change the Maximum Baud Rate
to 19200 (9600 for a CR10X), set the Beacon Interval to 0, set the Extra
Response Time to 15 seconds, and, if present, set the Delay Hangup to 200
ms.
You may change other settings in this configuration to suit your particular
application. Once complete, move to Step 6 to configure the datalogger.
FIGURE 5-5. PakBus Port Configuration
16