Call-Back Configuration for the CR800/CR1000 – MultiLogger Application Note #19 – Page 4 of 12
The second step involves configuring the
locations used for storing the call-back status and
the call-back abort used in the call-back
instructions. Use the menu item Program | Input
Locations or the Input Locations button to display
the Configure Input Locations form. Use the
Location selector to advance to the second
available user location at location 32. Alternately
advance to the end of the list to create new
locations.
Note: Some measurement types utilize User
Location 1 so User Location 2 is selected as
the first location to avoid potential conflicts.
Use the Alias edit to name the location
CallBackStatus.
Advance to the next location, location 33, and
configure the Alias edit to name the location
CallBackAbort.
Press Accept when finished labeled the Input
Locations.
Note: If you do not configure these locations errors similar
to that shown in the screenshot will display. The Alarm
Action programming utilizes these locations and without
defining them a compiler error will be generated.
To test the configuration and programming prior to
attempting the Update function, press the INFO button on
the Logger toolbar. This will build the program and display
a summary form when completed. Any errors in the
program will be shown for review.