User`s guide

Call-Back Configuration for the CR800/CR1000 – MultiLogger Application Note #19 – Page 12 of 12
The last step when using any of the call-back selections involves activating the Agent to accept the
incoming call-back requests.
Click on the Agent button on the Network Configuration toolbar to view the current Agent settings.
Configure the Schedule, or collection interval, to be used as the default if no call-back event is received.
Hint: You cannot use ASAP or Collect Once with call-back functionality.
Configure the Data Collection Method, when using the Data Recorded Since Last Collection a data
file named after the node name (in this case CR1000.DAT) will be used for recording data, when using
the Use Configuration File Settings the options in the Logger form will be used for collecting data and
naming the collected data file name. Generally Use Configuration File Settings is used.
Last configure the Failure Settings, make sure Stop Failure on Failure is UNCHECKED, otherwise a
communication failure on any node will stop the Agent, this includes the handling of incoming call-back
requests.
Press Start to start the Collection Agent.
Note: Call-back events will not be received and processed by the receiving computer unless the
Agent is started.