Instruction manual
AM16/32 Relay Analog Multiplexer
33
CLOCK PULSE
4: Do (P86)
1: 72 Pulse Port 2
5: Excitation with Delay (P22)
1: 1 EX Chan
2: 2 Delay w/EX (units=.01 sec)
3: 0 Delay after EX (units=.01 sec)
4: 1 mV Excitation
5: 0
MEASURES 1 THERMOCOUPLE PER LOOP
6: Thermocouple Temp (DIFF) (P14)
1: 1 Rep
2: 1 2.5 mV slow Range
3: 1 IN Chan
4: 1 Type T (Copper-Constantan)
5: 1 Ref Temp Loc REFTEMP
6: 2-- Loc [:TC #1 ]
7: 1 Mult
8: 0 Offset
MEASURES 1 SOIL MOISTURE BLOCK PER LOOP
7: AC Half Bridge (P5)
1: 1 Rep
2: 14 250 mV fast Range
3: 3 IN Chan
4: 2 Excite all reps w/EXchan 2
5: 250 mV Excitation
6: 18-- Loc [:SOIL M #1]
7: 1 Mult
8: 0 Offset
ENDS MEASUREMENT LOOP
8: End (P95)
DISABLES MULTIPLEXER
9: Do (P86)
1: 51 Set low Port 1
CALCULATES BRIDGE TRANSFORM ON SOIL MOISTURE BLOCKS
10: BR Transform Rf[X/(1-X)] (P59)
1: 16 Reps
2: 18 Loc [:SOIL M #1]
3: 1 Multiplier (Rf)
11: End Table 1 (P)
INPUT LOCATION LABELS:
1:REFTEMP 19:SOIL M #2
2:TC #1 20:SOIL M #3
3:TC #2 21:SOIL M #4
4:TC #3 22:SOIL M #5
5:TC #4 23:SOIL M #6