Instruction manual
AM16/32 Relay Analog Multiplexer
27
A problem with making full bridge measurements with this
configuration is that the resistance of the lead wire and multiplexer
relays can cause a voltage drop, reducing the excitation at the bridge.
The following section describes a configuration that compensates for
this by measuring the excitation at the bridge.
6.5 Full Bridges with Excitation Compensation
Sensor to Multiplexer wiring – With panel switch set to ”4X16” mode
you are 2 lines short for a six wire measurement. One solution is to
multiplex the four signal wires through the AM16/32, but bypass the
AM16/32 with excitation and ground wires. This means that the
sensors will be excited in parallel which causes a higher current drain,
possibly enough to exceed the current available from the datalogger's
excitation channel. Alternatively, the excitation and ground leads can
be multiplexed through an additional AM16/32 allowing the sensors to
be excited one at a time (Figure 16). In this case the 12V, GND, CLK,
and RES lines of the second multiplexer are wired in parallel with
those of the first, effectively widening the multiplexer to “8X16”.
Multiplexer to Datalogger wiring - Four leads from the COM ODD,
EVEN terminals connect to two sequential differential analog channels
in the datalogger. Excitation and ground are multiplexed by the
second AM16/32. Both multiplexers can be reset and clocked by the
same control ports and/or excitation channels to simplify
programming.
21x
CR7
CR10(X)
"4 X 16" Mode
AG
G
COM H (ODD)
COM L
COM H (EVEN)
COM L
ODD H
ODD L
EVEN H
EVEN L
SENSOR SHIELDS
COM
"4 X 16" Mode
EE
E/VX
LL
L
HH
H
LL
L
HH
H
COM H (ODD)
COM L
ODD H
ODD L
CR23X/
CR5000
FIGURE 16. Full Bridge Measurement with Excitation Compensation
CR23X/
21X CR1000/
CR7 CR10(X)
CR5000