User Manual
SP-LIT E Si licon Pyran ometer
12
5.5 Program Example 3, Average and Total Solar Radi ation
Wiring for Example 3
Color Function
Example CR1000
Program Channels
Used
White Radiation Signal 1H
Green Signal Reference 1L
Jumpered to
Clear Shield
EXAMP LE 3. Sample Instructions to Measure an Hourly Average Flux
and a Daily Total Flux with a CR1000
'CR1000
'Declare Variables
Public Slr_kW
Public Slr_MJ
'Declare Hourly Data Table
DataTable(Table1,True,-1)
DataInterval(0,60,Min,0)
Average(1,Slr_kW,IEEE4,0)
EndTable
'Declare Daily Data Table
DataTable(Table2,True,-1)
DataInterval(0,1440,Min,0)
Totalize(1,Slr_MJ,IEEE4,0)
EndTable
'Program
BeginProg
Scan(10,Sec,1,0)
'SP-LITE Pyranometer measurements Slr_MJ and Slr_kW:
VoltDiff(Slr_kW,1,mV25,1,True,0,_60Hz,1,0)
If Slr_kW<0 Then Slr_kW=0
Slr_MJ=Slr_kW*0.001
Slr_kW=Slr_kW*0.1
CallTable(Table1)
CallTable(Table2)
NextScan
EndProg