User Manual

LI200X Pyranometer
; set negative values to zero
2: If (X<=>F) (P89)
1: 3 X Loc [ SlrW ]
2: 4 <
3: 0 F
4: 30 Then Do
3: Z=F x 10^n (P30)
1: 0 F
2: 0 n, Exponent of 10
3: 3 Z Loc [ SlrW ]
4: End (P95)
; convert mV to MJ/m2 for 10 second execution interval
5: Z=X*F (P37)
1: 3 X Loc [ SlrW ]
2: 0.002 F
3: 4 Loc [ SlrMJ ]
; convert mV to W/m2
6: Z=X*F (P37)
1: 3 X Loc [ SlrW ]
2: 200.0 F
3: 3 Z Loc [ SlrW ]
7: If time is (P92)
1: 0 Minutes (Seconds --) into a
2: 60 Interval (same units as above)
3: 10 Set Output Flag High (Flag 0)
8: Set Active Storage Area (P80)
1: 1 Final Storage Area 1
2: 101 Array ID
9: Real Time (P77)
1: 1220 Year,Day,Hour/Minute (midnight = 2400)
10: Average (P71)
1: 1 Reps
2: 3 Loc [ SlrW ]
11: If time is (P92)
1: 0 Minutes (Seconds --) into a
2: 1440 Interval (same units as above)
3: 10 Set Output Flag High (Flag 0)
12: Set Active Storage Area (P80)
1: 1 Final Storage Area 1
2: 102 Array ID
8