User Manual

CS475, CS476, and CS477 Radar Water Level Sensor
Stage—the water level as measured in meters or feet. This measurement is
calculated using the Water Stage Setting and the Units setting.
Distance—the distance between the sensor and water surface. This value
will be reported in either meters or feet, depending on the Units setting.
Diagnostic Values—an error code. For example, Code 0 = OK, Code 13 =
error E013 (see Section 8.2, Diagnostics and Repair).
TABLE 8-1. Example of Start Measurement Command
Initial Command Response
0M!
Where zero is the
sensor address.
00023<cr><If>
Where (from left to right),
0—sensor’s address;
002—the amount of time (in seconds) that you must
wait before sending the send data command;
3—the number of values that will be placed in the
buffer.
Subsequent
Command
Response
0D0!
Where the first zero is
the sensor address.
0+100.050+25.000+0<cr><If>
Where (from left to right),
0—sensor’s address;
100.050—the stage in meters or feet;
25.000—the distance in meters or feet;
0—error code.
8.1.2 Check Unit Response
The Acknowledge Active command is used to check the presence of the sensor
on the bus (see TABLE 8-2).
TABLE 8-2. Acknowledge Active Command
Initial Command Response
a!
a<cr><If!>
Only the address is sent back in response.
8.1.3 Check for Valid Data
The aI! command gets the following identification information in response to
sending aI! (see TABLE 8-3).
Compatibility level: Version of SDI-12 protocol version; for example, 1.3.
Manufacturer’s Name: VEGA
22