User guide
CS210 Enclosure Humidity Sensor
'Define Data Tables
DataTable (Daily,1,-1)
DataInterval (0,1,Day,10)
Minimum (1,Batt_Volt,FP2,0,False)
Minimum (1,PanelTempC,FP2,False,False)
Maximum (1,PanelTempC,FP2,False,False)
Maximum (1,Enc_RH,FP2,False,False)
EndTable
'Main Program
BeginProg
Scan (10,Sec,0,0)
PanelTemp (PanelTempC,250)
Battery (Batt_volt)
'Measure CS210. Sensor is on all the time. Don't need a delay.
VoltSe (Enc_RH,1,mV2500,1,1,0,250,0.1,0)
'Set the sensor to 100% if it exceeds 100%.
If Enc_RH > 100 Then Enc_RH = 100
CallTable Daily
NextScan
EndProg
Example 2. Sample CR200 Program
'CR200 Series Datalogger
'To create a different opening program template, type in new
'instructions and select Template | Save as Default Template
'date:
'program author:
'SENSOR WIRING
'CS210
'Black: C2
'White: SE1
'Clear: G
'Declare Public Variables
'Example:
Public batt_volt
Public Enc_RH
'Define Data Tables
DataTable (Daily,1,-1)
DataInterval (0,24,hr)
Minimum (1,batt_volt,0,0)
Maximum (1,Enc_RH,False,0)
EndTable
4