Appendix C. Serial Port Pin Outs 
C.1  RS-232 Communications Port 
C.1.1  Pin-Out 
Pin configuration for the CR200(X) RS-232 9-pin port is listed in TABLE. 
CR200(X) RS-232 Pin-Out p. 21.  
The CR200(X) RS-232 port is a DCE (Data Communication Equipment) device. 
A limited version of the RS-232 port is supported with no hardware flow 
control. The most common use of the Datalogger's RS-232 port is a connection 
to a computer DTE device. A standard DB9-to-DB9 cable can connect the 
computer DTE device to the Datalogger DCE device.  
The CR200(X) RS-232 port is not electrically isolated. Connection to an AC 
powered computer may cause ground loops leading to measurement problems. 
Maximum input = ±25 V 
Maximum Output = ±13 V 
Typical Output = ±5.4 V 
The following table describes the Datalogger's RS-232 pin function with 
standard DCE naming notation. 
Table 28. CR200(X) RS-232 Pin-Out 
PIN: Pin number 
O: Signal Out of the CR200(X) to a RS-232 device 
I: Signal Into the CR200(X) from a RS-232 device 
PIN  DCE Function  Logger Function  I/O  Description 
1 
N/A 
Not Connected 
2  TX  TXD  O  Asynchronous data Transmit 
3  RX  RXD  I  Asynchronous data Receive 
4 
N/A 
Not Connected 
5  GND  GND 
Ground 
6  DSR  DTR  O  Data Terminal Ready 
7 
N/A 
Not Connected 
8  CTS  RTS  O  Request to send 
9 
N/A 
Not Connected 