User Manual

223 Delmhorst Cylindrical Soil Moisture Block
19: Real Time (P77) ;Output Day and Hour/Minute
1: 220 Day,Hour/Minute (midnight = 2400)
20: Sample (P70) ;Output resistances and Water Potentials
1: 64 Reps
2: 1 Loc [ BlockR_1 ]
7.2.5.3 Example 21X Program
21X
Multiplexer
FIGURE 7-5. Wiring for example 21X program
*Table 1 Program
01: 10 Execution Interval (seconds)
01: Set Port (P20) ;Enable multiplexer
1: 1 Set High
2: 1 Port Number
02: Beginning of Loop (P87) ;Start of measurement loop
1: 0 Delay
2: 16 Loop Count
03: Excitation with Delay (P22) ;Clock Multiplexer to next channel
1: 1 Ex Channel
2: 1 Delay w/Ex (units = 0.01 sec)
3: 1 Delay After Ex (units = 0.01 sec)
4: 5000 mV Excitation
04: Step Loop Index (P90) ;Step index by 2 each pass through loop
1: 2 Step
18