User Manual
223 Delmhorst Cylindrical Soil Moisture Block 
19: Real Time (P77)    ;Output Day and Hour/Minute 
  1:    220  Day,Hour/Minute (midnight = 2400) 
20: Sample (P70)    ;Output resistances and Water Potentials 
 1:    64  Reps 
  2:    1  Loc [ BlockR_1 ] 
7.2.5.3 Example 21X Program 
21X 
Multiplexer 
FIGURE 7-5. Wiring for example 21X program 
*Table 1 Program 
 01:   10  Execution Interval (seconds) 
01: Set Port (P20)    ;Enable multiplexer 
 1:    1  Set High 
 2:    1  Port Number 
02: Beginning of Loop (P87)  ;Start of measurement loop 
 1:    0  Delay 
 2:    16  Loop Count 
03: Excitation with Delay (P22)  ;Clock Multiplexer to next channel 
 1:    1  Ex Channel 
  2:    1  Delay w/Ex (units = 0.01 sec) 
  3:    1  Delay After Ex (units = 0.01 sec) 
 4:    5000  mV Excitation 
04: Step Loop Index (P90)  ;Step index by 2 each pass through loop 
 1:    2  Step 
18 