7.4  Programming 
This section is for users who write their own programs. A datalogger program 
to measure this sensor can be created using Short Cut. You do not need to read 
this section to use Short Cut. 
7.4.1  Wind Speed 
Wind speed is measured with the Pulse Count instruction (PulseCount() in 
CRBasic and Instruction 3 in Edlog). Use the low level AC configuration. 
For dataloggers programmed with Edlog, specify configuration code 21 to 
output frequency in hertz. 
The expression for wind speed (U) is: 
  U  =  MX + B 
 where 
 M = multiplier 
  X  =  number of pulses per second (Hertz) 
 B = offset 
TABLE 7-3 lists the multipliers (M) and offsets (Off) to obtain meters/second 
or miles/hour when the Pulse Count instruction is configured to output the 
result in hertz. 
TABLE 7-3. Wind Speed Multiplier 
(With Pulse Channel Configuration Set to Low Level AC, Output “Hz”) 
Model  Meters/Second  Miles/Hour 
03002 / 03101  M = 0.750 
Off = 0.2 
M = 1.677 
Off = 0.4 
*When the pulse channel configuration is set to Low Level AC, output 
“counts”, the multiplier above is divided by the execution interval in seconds. 
7.4.2  Wind Direction 
The wind vane is coupled to a 10 kΩ potentiometer, which has a 8 degree 
electrical dead band between 352 and 360 degrees. 
The CR200(X) dataloggers use the ExDelSE() instruction to measure wind 
direction. All other CRBasic dataloggers use the BRHalf() instruction. Edlog 
dataloggers (CR510, CR10X, CR23X) use Edlog Instruction 4—Excite, Delay 
(P4). 
Excitation voltages, range codes, and multipliers for Campbell Scientific 
dataloggers are listed in TABLE 7-4. Appendix B has additional information 
on the BRHalf() measurement instructions. 