Measurement and Control Module Operators Manual

SECTION 7. MEASUREMENT PROGRAMMING EXAMPLES
7-18
FIGURE 7.16-3. Hook up to AVW1
Program: AVW1 & CR10 USED TO
MEASURE 1 GEOKON VIBRATING WIRE
SENSOR.
* 1 Table 1 Programs
01: 60 Sec. Execution Interval
01: P4 Excite,Delay,Volt(SE)
01: 1 Rep
02: 15 2500 mV fast Range
03: 1 IN Chan
04: 1 Excite all reps w/EXchan 1
05: 1 Delay (units .01sec)
06: 2500 mV Excitation
07: 1 Loc [:TEMP ]
08: .001 Mult
09: 0 Offset
02: P55 Polynomial
01: 1 Rep
02: 1 X Loc TEMP
03: 1 F(X) Loc [:TEMP ]
04: -104.78 C0
05: 378.11 C1
06: -611.59 C2
07: 544.27 C3
08: -240.91 C4
09: 43.089 C5
03: P28 Vibrating Wire (SE)
01: 1 Rep
02: 2 IN Chan
03: 1 Excite all reps w/EXchan 1
04: 24 Starting Freq. (units=100 Hz)
05: 32 End Freq. (units=100 Hz)
06: 500 No. of Cycles
07: 0 Rep delay (units=.01sec)
08: 2 Loc [:PRESSURE ]
09: -34.836 Mult