Datasheet
SINEAX TP619
Potentiometric Signal Converter
Camille Bauer Data sheet TP619 Le – 03.09 1
Potentiometric to DC isolating amplifi er
Features / Benefi ts
● Input: – Resistor
– Rheostat
– Potentiometer
● Output: Current or voltage
● Accuracy: 0.2%
● 3-way galvanic isolation
● Screw-fi t terminals (removable)
● DIN rail mounting
● Power supply: 19 … 40 V DC, 19 … 28 V AC
General Data
Power supply 19 … 40 V DC, 19 … 28 V AC
Accuracy < 0.2%
Status indicators (LED) Power
Galvanic isolation
Power supply / input / output at
1500 V AC, digital
Hot swapping Yes
Power consumption 2.5 W
Installation class 2
Humidity Up to 90% at + 40 °C (not condensing)
Conformity CE
Housing
Terminal housing for mounting on
35 mm DIN 46277.
“V0” self-extinguishing glass fi lled nylon
case
Response time 60 ms
DIP Switch
– Input signals setup
– Output signal setup
Dimensions 17.5 x 100 x 112 mm (w x h x d)
Weight 140 g
Operating temperature 0 … 50 °C
Connections
Plug-in screw clamp terminal blocks,
wires up to 2.5 mm
2
IP protection IP 20
Input Data
Resistance with connection
Rheostat (2-wire), ranges 0 … 300 Ω
(I = 6 mA), 0 … 500 Ω (I = 3.6 mA) and
0 … 1 kΩ (I = 1.8 mA)
Resistance with connection to potentio-
meter (3 wires) (Vref = 1.8 V DC)
Output Data
Current
0 … 20 mA, 4 … 20 mA
Higher load resistance: 600 Ω
Voltage
0 … 5 V DC, 1 … 5 V DC,
0 … 10 V DC and 2 … 10 V DC
Lower load resistance: 2.5 Ω