Installation Instructions

- 10 - Mseries
Terminal Identification Tables:
Power Supply Board
Terminal Function/Description
Legend
L, G, N Connect 115VAC 60Hz to these terminals: L to hot, N to neutral, G to ground.
- DC + AL300ULM - 12VDC/24VDC @ 2.5 amp to MOM5 board (power limited).
AL400ULM - 12VDC @ 4 amp or 24VDC @ 3 amp to MOM5 board (power limited).
AL600ULM - 12VDC/24VDC @ 6 amp to MOM5 board (non-power limited).
AL1012ULM - 12VDC @ 10 amp to MOM5 board (non-power limited).
AL1024ULM - 24VDC @ 10 amp to MOM5 board (non-power limited).
AC FAIL Indicates loss of AC power, e.g. connect to audible device or alarm panel. Relay
NO, C, NC normally energized when AC power is present. Contact rating 1 amp @ 28VDC.
AC or brownout fail is reported within 1 minute of event. To delay reporting of up to
6 hrs., cut ā€œAC delayā€ jumper and reset power to unit.
BAT FAIL Indicates low battery condition, e.g. connect to alarm panel. Relay normally
NO, C, NC energized when DC power is present. Contact rating 1 amp @ 28VDC.
A removed battery is reported within 5 minutes. Battery reconnection is reported
within 1 minute.
Low battery threshold:
12VDC output threshold set @ approximately 10.5VDC (N/A for AL1024ULM),
24VDC output threshold set @ approximately 21VDC.
+ BAT - Stand-by battery connections. AL300ULXB, AL400ULXB and AL600ULXB (Power Supply
Board) maximum charge current is .7 amp. AL1024ULXB (Power Supply Board)
maximum charge current is 3.6 amp.
MOM5 - Output Module
Terminal Legend Function/Description
--- DC INPUT + 12VDC or 24VDC from power supply.
TRIGGER Dry normally open [NO] or normally closed [NC] supervised (2.2K EOL resistor)
input trigger. A short or open circuit will transfer power from terminals marked
[POS. (+) DC OUTPUT (STAND-BY)] to terminals marked
[POS (+) DC OUTPUT (ALARM)].
--- INPUT + Wet (5-30VDC) input trigger. Applying voltage to these terminals in the polarity shown
will transfer power from terminals marked [POS. (+) DC OUTPUT (STAND-BY)] to
terminals marked [POS (+) DC OUTPUT (ALARM)] (e.g. fire alarm control panel
indications circuit).
NEG 1 THRU NEG 5 Supplies constant negative (-) voltage.
POS (+) DC OUTPUT Supplies positive (+) voltage when dry trigger input or fire
(ALARM) 1-5 alarm wet trigger input is applied.
POS (+) DC OUTPUT Supplies positive (+) voltage in normal condition.
(STAND-BY) 6-10 Power is removed when dry trigger input or fire alarm wet trigger input is applied.
NC, C, NO When the MOM5 is triggered the terminals marked [C and NO] will open and the
DRY OUTPUT terminals marked [C and NC] will close. This output is used to trigger auxiliary devices.
(e.g. HVAC Shutdown, Elevator Recall etc.) Contact rating 1 amp @ 28VDC.
NC, C, NO Form ā€œCā€ contacts used for reporting no voltage is present at [-- DC input +]
POWER FAIL terminals. Under normal conditions, terminals marked [NO and C] are open, [NC and C]
are closed. A loss of power causes terminals marked [NO and C] to close and [NC and C]
to open. Contact rating 1 amp @ 28VDC.