User's Guide

Table Of Contents
PTP 250 User Guide Grounding and lightning protection
phn-2182_003v004 (Oct 2011)
UNDER DEVELOPMENT
2-17
General protection requirements
To adequately protect a PTP 250 installation, both ground bonding and transient voltage
surge suppression are required.
Basic requirements
The following basic protection requirements must be implemented:
The ODU must be in ‘Zone B’ (see Lightning protection zones on
page 2-16).
A lightning protection unit (LPU) must be installed within 600 mm (24 in) of the point
at which the drop cable enters the building or equipment room.
The drop cable must be bonded to the supporting structure in order to prevent
lightning creating a potential between the structure and cable, which could cause
arcing, resulting in fire risk and damage to equipment.
The drop cable must be grounded at the building entry point.
The drop cable must not be laid alongside a lightning air terminal.
All grounding cables must be a minimum size of 10 mm
2
csa (8AWG), preferably 16
mm
2
csa (6AWG), or 25 mm
2
csa (4AWG).
Grounding cable requirements
When routing, fastening and connecting grounding cables, the following requirements
must be implemented:
Grounding conductors must be run as short, straight, and smoothly as possible, with
the fewest possible number of bends and curves.
Grounding cables must not be installed with drip loops.
All bends must have a minimum radius of 203 mm (8 in) and a minimum angle of 90°
(Figure 2-2). A diagonal run is p
referable to a bend, even though it does not follow the
contour or run parallel to the supporting structure.
All bends, curves and connections must be routed towards the grounding electrode
system, ground rod, or ground bar.
Grounding conductors must be securely fastened.
Braided grounding conductors must not be used.
Approved bonding techniques must be used for the connection of dissimilar metals.