PTP 500 Series User Guide phn-1115-000v001
MOTOROLA, Inc. Point-to-Point Wireless Bridges – PTP 500 Series Software Release PTP 500-01-xx System User Manual March 7 th , 2008 Ref: PHN-1115-00.01 Copyright Information This document is the confidential property of Motorola, Inc. and without its prior written consent may not be copied or released to third parties. MOTOROLA, the stylized M Logo and all other trademarks indicated as such herein are trademarks of Motorola, Inc. Reg. U.S. Pat & Tm. Office. PTP 500 is a trademark of Motorola, Inc.
The system has been tested for compliance to both US (FCC) and European (ETSI) specifications. It has been shown to comply with the limits for emitted spurious radiation for a Class B digital device 1, pursuant to Part 15 of the FCC Rules in the USA and appropriate European ENs. These limits have been designed to provide reasonable protection against harmful interference.
Regulations applicable to 5.4GHz PTP 500 Series Bridge variant Examples of Regulatory Limits at 5.
Regulations applicable to 5.8GHz PTP 500 Series Bridge variant Examples of Regulatory Limits at 5.
General Notice Applicable to Europe This equipment complies with the essential requirements for the EU R&E Directive 1999/5/EC. The use of 5.8GHz for Point to Point radio links is not harmonized across the EU. However, the regulatory situation in Europe is changing and the radio spectrum may become available in other countries in the near future. Please contact Motorola for the latest situation. Notes: UK Registration of Links – OfCom, The application form may be found at http://www.ofcom.org.
Contents 1 1.1 1.2 1.2.1 2 2.1 2.1.1 3 3.1 3.2 3.2.1 3.2.2 3.2.3 3.3 3.3.1 3.3.2 3.3.3 3.3.4 3.3.5 3.3.6 3.3.7 3.3.8 3.4 4 5 5.1 5.2 5.3 5.3.1 5.3.2 5.3.3 5.4 5.5 5.5.1 5.5.2 5.6 5.6.1 5.6.2 5.7 5.8 5.9 5.10 6 6.1 6.1.1 6.1.2 6.1.3 About This User Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Interpreting Typeface and Other Conventions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Getting Additional Help . . . . . . . . .
6.1.4 6.1.5 6.1.6 7 7.1 7.2 7.3 7.4 7.5 7.6 7.7 7.7.1 7.7.2 7.7.3 7.7.4 7.7.5 7.7.6 7.7.7 7.7.8 7.7.9 7.7.10 7.7.11 8 8.1 8.1.1 8.2 8.3 8.3.1 8.3.2 8.3.3 8.3.4 8.3.5 8.3.6 8.3.7 8.3.8 8.3.9 8.3.10 8.3.11 8.3.12 8.3.13 8.3.14 8.3.15 9 9.1 9.2 9.3 9.4 Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 5.4 GHz Product Variant - Link Loss, Output Power and System Thresholds versus Modulation Mode . . . . . . . . . . . .
.5 10 10.1 10.1.1 10.1.2 10.1.3 10.2 10.2.1 10.2.2 11 11.1 11.1.1 11.2 11.3 11.3.1 11.3.2 11.4 12 12.1 12.2 12.3 12.4 13 13.1 13.2 13.2.1 13.2.2 13.2.3 13.3 13.3.1 13.3.2 13.3.3 13.4 13.5 13.6 13.6.1 13.6.2 13.6.3 13.6.4 13.7 13.7.1 13.7.2 13.7.3 13.7.4 13.7.5 13.7.6 13.7.7 13.7.8 13.7.9 Reboot . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Fault Finding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
13.7.10 13.7.11 13.7.12 13.8 13.8.1 13.8.2 14 15 15.1 15.1.1 15.1.2 15.2 15.2.1 15.2.2 15.2.3 16 16.1 16.2 16.2.1 16.2.2 16.3 16.3.1 16.3.2 16.4 16.5 16.5.1 16.5.2 17 17.1 17.1.1 17.1.2 17.1.3 17.1.4 17.1.5 17.1.6 17.2 17.3 17.3.1 17.3.2 17.4 17.5 17.5.1 17.5.2 17.6 17.7 17.7.1 18 19 Completing the Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Antenna Cable Fixing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
List of Figures 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 Typical PTP 500 Series Bridge Deployment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PTP 500 Series Bridge Outdoor Unit (ODU) with PTP-LPU . . . . . . . . . . . . . . . . . . . . Power Indoor Unit (PIDU Plus) – PTP 500 Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PIDU Plus Recovery Switch Location . . . . . . . . .
48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 5.8 GHz and 5.4 GHz Variants - Installation Wizard Confirm Configuration . . . . . . . 90 Reboot Confirmation Pop Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91 5.8 GHz and 5.4 GHz Variant - Disarm Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92 Optional Post Disarm Configuration 2 . . .
97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 PTP LPU End Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Simplified Circuit Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PTP LPU test Points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
List of Tables 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Font types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Admonition types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Power Compliance Margins . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Contact Information . . . . . . . . . .
About This User Guide 1 About This User Guide This guide covers the installation, commissioning, operation and fault finding of the Motorola PTP 500 Series of Point-to-Point Wireless Ethernet Bridges. 1.1 Interpreting Typeface and Other Conventions This document employs distinctive fonts to indicate the type of information, as described in Table 1. Font Type of Information variable width bold Selectable option in a graphical user interface or settable parameter in a web-based interface.
About This User Guide This document also employs a set of consistently used admonitions. Each type of admonition has a general purpose that underlies the specific information in the box. These purposes are indicated in Table 2. Admonition General Message Label Note Informative content that may: • • • • • Defy common or cursory logic. Describe a peculiarity of the 500 Series solutions implementation. Add a conditional caveat. Provide a reference.
About This User Guide 3. Ask your Motorola products supplier to help. 4. Gather information from affected units such as: a. b. c. d. the IP addresses and MAC addresses the software releases the configuration of software features any available diagnostic downloads 5. Escalate the problem to Motorola Technical Support as follows. You may either: a. Send e-mail to support.ptp@motorola.com b. Call our 24x7 Technical Support Center on +1 (0) 877 515 0400 (Worldwide) or +44 (0) 808 234 4640 (UK Customers).
Avoiding Hazards 2 Avoiding Hazards 2.1 Preventing Overexposure to RF Energy Caution To protect from overexposure to RF energy, install the radios for the 500 family of PTP wireless solutions so as to provide and maintain the minimum separation distances from all persons as shown in Table 3. When the system is operational, avoid standing directly in front of the antenna. Strong RF fields are present when the transmitter is on.
Avoiding Hazards Rearranging terms to solve for distance yields d= P.G 4πS (2) 2.1.1.1 Calculated Distances and Power Compliance Margins Table 3 shows calculated minimum separation distances d, recommended distances and resulting power compliance margins for each frequency band and antenna combination. Band 5.4 GHz 5.8 GHz Antenna Max Average Transmit P Power in (Watt) Burst (Watt) Variable G S (W/m2 ) D (m) Recommended Distance (m) Power Compliance Margin 1 15.9 Integrated 0.
Getting Started 3 Getting Started 3.1 For Your Safety WARNING: Use extreme care when installing antennas near power lines. WARNING: Use extreme care when working at heights. WARNING: The Outdoor Unit (ODU) for the PTP 500 Series Bridge must be properly grounded to protect against lightning. It is the user’s responsibility to install the equipment in accordance with Section 810 of the National Electric Code, ANSI/NFPA No.70-1984 or Section 54 of the Canadian Electrical Code.
Getting Started 3.2.1 Who Should Use This Guide? The guide is for use by the system installer and the end user IT professional. The system installer will require expertise in the following areas: • • • Outdoor radio equipment installation Network configuration Use of web browser for system configuration, monitoring and fault finding 3.2.2 Contact Information Postal Address: Motorola, Inc. Unit A1, Linhay Business Park, Eastern Road, Ashburton, Devon. TQ13 7UP United Kingdom Web Site: http://www.motorola.
Getting Started 3.3 Product Description This User Manual is specifically written for the 500 family of point-to-point broadband wireless solutions. The PTP 500 Series Bridge has been developed to provide Point-to-Point data connectivity via a 5.4 GHz or 5.8 GHz wireless Ethernet bridge operating at broadband data rates. The PTP 500 Series Bridge is aimed at a wide range of applications.
Getting Started A pair of units is normally supplied pre-configured as a link. The network connection to a PTP 500 Series Bridge is made via a 100BaseT Ethernet connection. Power is provided to the ODU over the 100BaseT Ethernet connection using a patented nonstandard powering technique. Power is fed into the PTP 500 Series Bridge PIDU Plus from the mains via a standard “figure of eight” mains plug. Connection between the ODU and PIDU Plus is made using standard CAT5e outdoor UV resistant cable.
Getting Started 3.3.1 The Outdoor Unit (ODU) The ODU is a self-contained unit. It houses both radio and networking electronics. The ODU for the PTP 500 Series Bridge should only be deployed using the supplied PTP 500 Series Bridge PIDU Plus. Figure 2 shows an installation example of a PTP 500 Series ODU with a Motorola lightning protection unit (PTP-LPU).
Getting Started 3.3.2 PIDU Plus – PTP 500 Series Bridge The PTP 500 Series Bridge PIDU Plus is used to generate the ODU supply voltage from the mains supply and inject this supply voltage into the 1000BaseT Ethernet connection to the ODU. Connection uses a CAT5e cable using standard RJ45 wiring. CAUTION: Care should be taken not to connect equipment other than an ODU for the PTP 500 Series Bridge to a PIDU Plus ODU port as equipment damage may occur.
Getting Started The Recovery switch is used to recover the unit from configuration errors or software image corruption. To put a PTP 500 Series Bridge into Recovery mode the Recovery switch should be pressed then the power applied. The Recovery switch should be kept pressed for at least 30 seconds after the power has been applied. Full instruction on the recovery mode can be found in Section 9 “Recovery Mode”.
Getting Started 3.3.3 Redundancy and Alternate Powering Configurations NOTE: The use of DC supplies of less than 55v will reduce the usable distance between the PIDU Plus and ODU see Figure 6. Figure 6 PTP 500 Series Bridge PIDU Plus to ODU Cable Length Graph CAUTION: The maximum distance from the ODU to the connected network equipment is 100m (330 ft) when using 100BaseT. 3.3.3.1 External DC Supply Only For use where there is no mains supply.
Getting Started 3.3.3.2 External DC Supply and AC Supply To give redundancy through the use of mains and DC supply. Figure 8 External DC Supply and AC Supply 3.3.3.3 External DC Supply and Redundant AC Supply To guard against mains failure, DC supply failure of PTP 500 Series Bridge PIDU Plus failure.
Getting Started 3.3.4 Remote LEDs and Recovery Switch The PTP 500 Series Bridge PIDU Plus provides a facility to connect remote LEDs and Recovery switch allowing the PIDU Plus to be mounted inside an enclosure. At the left hand end of the PIDU Plus under the ODU connection cover can be found a PCB header and three jumpers. Jumpers J906 and J907 should be removed and connection to the remote LEDs and Recovery switch made to J908 as shown in Figure 10. Figure 10 Remote LED and Recovery Switch Wiring 3.3.
Getting Started Caution: Failure to use the recommended (or equivalent) standard of cable may invalidate the system’s safety certification. The cable used to connect the PTP 500 Series Bridge PIDU Plus to the users Network Equipment can be any standard CAT5e Cable. The PIDU Plus to ODU and the PIDU Plus to Network Equipment cables may be unscreened (UTP) or screened (STP). However, unscreened cables reduce the system’s ability to cope with nearby lightning strikes.
Getting Started 3.4 Warranty Motorola’s standard hardware warranty is for one (1) year from date of shipment from Motorola or a Motorola Point-to-Point Distributor. Motorola warrants that hardware will conform to the current relevant published specifications and will be free from material defects in material and workmanship under normal use and service.
Product Architecture 4 Product Architecture The PTP 500 Series Bridge consists of an identical pair of units deployed one at each end of the link. The radio link operates on a single frequency channel in each direction using Time Division Duplex (TDD). One unit is deployed as a master and the other as a slave. The master unit takes responsibility for controlling the link in both directions.
Product Architecture Figure 11 PTP 500 Series Bridge Layer Diagram Each unit in the link is manageable through an IP connection. Standard IP protocols are utilized for all management functions e.g., HP, SNMP, etc. The unit can be configured to use VLAN tags on the management interfaces. The PTP 500 Series Bridge is fully software upgradeable. New software images are first downloaded from the Motorola website http://www.motorola.com/ptp to a convenient computer.
General Considerations 5 General Considerations 5.1 Spectrum Planning The PTP 500 Series Bridge has four frequency variants in its product range. Band Definition Frequency Coverage Variable Channel Channel Width Raster 5.4 GHz ETSI 5 GHz band B, USA UNII Band 5470-5725 MHz 15 MHz 5 MHz 5.8 GHz USA ISM Band / ETSI 5 GHz band C 5725-5850 MHz 15 MHz 5 MHz Table 5 PTP 500 Series Bridge Variants Note: for 5.4 GHz and 5.8 GHz, use of the product is allowed according to local regulations.
General Considerations 5.2 Region Codes The PTP 500 Series Bridge uses a system of Region Codes to control the operation of the radio link. The Region Code is set by a License Key. Caution: To meet the regulatory requirements of your region you should set the correct Region Code by obtaining a new License Key from your reseller or distributor. Region Frequency Code Band Regulatory Body or Countries Max Tx Power 1 5.8 GHz FCC Compliant (e.g. USA, Canada, Taiwan, Brazil) 25 dBm None 2 5.
General Considerations Region Frequency Code Band Regulatory Body or Countries Max Tx Power 11 5.4 GHz Korea 20 dBm 43 dBm Band restricted : 5725 MHz to 5825 MHz 12 5.4 GHz USA 7 dBm 30 dBm Radar Avoidance Enabled 13 5.4 GHz Australia, Canada 7 dBm 30 dBm Radar Avoidance Enabled Weather; Radar Band (5600 to 5650 MHz) barred 16 2.5 GHz USA 23 dBm >=63 dBm Licensed Band operation. Note Power reduction in the Upper Band. 18 2.
General Considerations Note: For Region Code 16, the EIRP limit is approximately 63 dBm + 10 x Log(360/Antenna Azimuth BW. When shipped from the factory units 3 are configured as follows: • PTP 500 Series Bridge 5.4 GHz – Region Code 26 4 • PTP 500 Series Bridge 5.8 GHz – Region Code 1 5.3 Operational Restrictions 5.3.
General Considerations 5.3.2 RTTT Avoidance and Other Channel Use Restrictions Where regulatory restrictions apply to certain channels these channels are barred. The user should note that the number of channels barred is dependent on the channel raster selected. For example see the effect of the UK RTTT channel restrictions in Figure 12. Barred channels are indicated by a “No Entry” symbol displayed on the “Spectrum Management” web page, see Section 8.3.
General Considerations 5.5 5.4 GHz Specific Frequency Planning Considerations Adjustment of the lower centre frequency allows the operator to slide the available frequency settings up and down the 5.4 GHz band. See Figure 13.
General Considerations 5.6 5.8 GHz Specific Frequency Planning Considerations Adjustment of the lower center frequency allows the operator to slide the available frequency settings up and down the 5.8 GHz bands. Figure 14 shows the available spectrum.
General Considerations Channel Center Frequency Maximum Output Power (dBm) (MHz) Channel Bandwidth (MHz) 15 5735 25 5736 25 5737 25 5738 25 5739 - 5838 25 5740 25 5742 - 5832 25 5839 26 5840 26 Table 6 5.8 GHz Band Edge Tx Power Reduction 5.7 Distance The PTP 500 Series Bridge will operate at ranges from 100 m (330 ft) to 200 km (124 miles), within 3 modes: 0-40km (0-25 miles), 0-100km (0-62 miles) and 0-200km (0-124 miles).
Site Planning 6 Site Planning 6.1 Site Selection Criteria The following are guidelines for selecting the installation location of the ODU and PIDU Plus for a PTP 500 Series Bridge. 6.1.
Site Planning 6.1.4 Definitions The equipment capability is given in Table 7, Table 9 (IP Mode) and Table ??, Table 10 (TDM Mode). Each table gives Link Loss Output Power and System Thresholds for PTP 500 Series Bridge in all modulation modes for the channel bandwidth 15 MHz. Adaptive Modulation will ensure that the highest throughput that can be achieved instantaneously will be obtained taking account of propagation and interference.
Site Planning 6.1.5 5.4 GHz Product Variant - Link Loss, Output Power and System Thresholds versus Modulation Mode Table 7 and Table 8 show respectively sensitivity figures for IP and TDM respectively. Modulation Mode Threshold Value (dBm) Output Power (dBm) Maximum Link Loss (dB) Channel Bandwidth (MHz) 15 MHz 256QAM 0.75 dual -65.02 +21 64 QAM 0.83 dual -69.63 +21 133.02 137.63 64QAM 0.67 dual -73.22 +22 142.22 16QAM 0.75 dual -76.59 +23 146.59 16QAM 0.50 dual -80.72 +24 151.
Site Planning 6.1.6 5.8 GHz Product Variant - Link Loss, Output Power and System Thresholds versus Modulation Mode Table 9 and Table 10 show respectively sensitivity figures for IP and TDM respectively. Modulation Mode Threshold Value (dBm) Output Power (dBm) Maximum Link Loss (dB) Channel Bandwidth (MHz) 15 MHz 256QAM 0.75 dual -65.02 +21 64 QAM 0.83 dual -69.63 +21 133.02 137.63 64QAM 0.67 dual -73.22 +22 142.22 16QAM 0.75 dual -76.59 +23 146.59 16QAM 0.50 dual -80.72 +24 151.
Installation 7 Installation Motorola recommends that only qualified personnel undertake the installation of a PTP 500 Series Bridge solution. 7.1 Preparation Before proceeding with the installation you should: • • • • • Check the contents of all packages against the parts lists shown in the packing list. Ensure that you have the correct tools for the job. Ensure that you are qualified to undertake the work. Ensure that you have taken the correct safety precautions.
Installation 7.5 Legal Disclaimer IN NO EVENT SHALL MOTOROLA, INC. BE LIABLE FOR ANY INJURY TO ANY PERSONS OR ANY DAMAGE CAUSED DURING THE INSTALLATION OF THE MOTOROLA PTP 500 SERIES PRODUCT. 7.6 Mounting the ODUs The ODU mounting bracket is designed to ease installation by fixing the bracket to a pole and then bringing the ODU into position using a single bolt fixing. The ODU should be mounted using the following steps ensuring that the cable entry is at the bottom.
Installation The enclosure and mounting brackets of the PTP 500 Series Bridge product range are capable of withstanding wind speeds up to 151mph (242kph). The installer should ensure that the structure the bridge is fixed to is also capable of withstanding the prevalent wind speeds and loads. See Section 12 "Wind Loading".
Installation The cable should be assembled as shown in Figure 17: Figure 17 Correct Cable Preparation for the Recommended Cable Both ends of the ODU cable are terminated in the same way. The above procedure should be repeated for the PIDU Plus end of the cable when the cable routing process is complete. This assumes that the installation uses PTP LPUs. If not, then the PIDU Plus end of the cable does not require a Gland, but just the RJ45. NOTE: The PIDU Plus end of the cable does not use a cable gland.
Installation Figure 18 shows a completed ODU to PIDU Plus cable. Figure 18 Completed ODU Connector CAUTION: Do not over tighten the glands as the internal seal and structure may be damaged. See Figure 19 for an example of an over tightened cable gland. Figure 19 Warning Not To Over tighten Cable Gland 7.7.
Installation 7.7.3 Making the PTP 500 Series Bridge PIDU Plus Connection At The ODU The following procedure describes how connection is made at the ODU. It is often easier to carry out this procedure on the ground or a suitable surface prior to mounting the ODU. Ensure that no power is connected to the PIDU Plus or present on the cable before connecting the ODU. Step 1: Assemble the cable as described in 5.7.
Installation Should it be necessary to disconnect the PIDU Plus to ODU cable at the ODU, this can be achieved by removing the weather proofing gland and depressing the RJ45 locking tab with a small screwdriver as shown below: Figure 22 Disconnecting the ODU CAUTION: Ensure that power is removed from the system at the PIDU Plus to prevent damage to the ODU while making or breaking the connection. 7.7.
Installation 7.7.7 Making the ODU Connection at the PTP 500 Series Bridge PIDU Plus The ODU is connected to the PIDU Plus by means of a concealed RJ45 connector. The RJ45 connection has been placed inside the PIDU Plus hinged cover to prevent the user from inadvertently plugging other equipment into the ODU RJ45 socket.
Installation 7.7.8 Making the Network Connection at The PIDU Plus – PTP 500 Series Bridge The Network connection is made by connecting the user’s Network Equipment directly to the PIDU Plus LAN port as shown in Figure 23. Figure 23 Making the Network Connection at the PIDU Plus 7.7.9 Mounting the PTP 500 Series Bridge PIDU Plus This step is optional. Motorola recommends that you mount the PIDU Plus on a wall or other suitable mounting surface.
Installation CAUTION: The PIDU Plus is not waterproof and should be mounted away from sources of moisture. If mounted outdoors, the unit should be mounted in a rain proof enclosure, preferably ventilated. It is also recommended that you fit a drip loop on the PIDU Plus to ODU cable to ensure that any moisture that runs down the cable into the cabinet or enclosure cannot enter the PIDU Plus. As shown in Figure 24.
Installation as a hub/switch (and auto-sensing MDI/MDIX cross over is employed), connection can be made directly to the computer using a standard CAT 5 patch cable. Before physical installation takes place the units to be installed should be set up as described in the Section 8.3.4 "Install Pages". It is recommended that this procedure be carried out on the bench before physical installation commences.
Installation may be suffering from interference or a fast fading link. Installing in this situation may not give a reliable link. The cause of the problem should be investigated. For the ease of alignment, both Master and Slave units use the install tones in the same way but with some small behavioral differences. This allows the installer to install the Slave unit first and carry out the initial alignment with the Master unit if desired.
Web Page Reference 8 Web Page Reference The web user interface has three main sections. The home page presents to the operator a high level summary of the PTP 500 Series Bridge point-to-point wireless link. The status page presents a more detailed set of system parameters describing the performance of the wireless link together with other key system performance metrics. The final section is the system administration section.
Web Page Reference 8.1 Home Page – PTP 500 Series Bridge The home page for the PTP 500 Series Bridge has been designed to display a high level summary of the status of the wireless link and associated equipment. The home page (Figure 26) normally displays four key system attributes: Wireless Link Status: The Wireless Link Status attribute displays the current status of the PTP 500 Series Bridge wireless link. A state of ‘Up’ on a green background indicates that a pointto-point link is established.
Web Page Reference Figure 27 Alarm Warning Triangle The following system alarms are defined: Region Code: The region code prohibits the wireless unit from operating outside the regulated limits. An invalid region code indicates a corrupted license key. Note that a change of state may generate an SNMP trap and/or SMTP email alert. Install Status: A non-OK value indicates that signaling was received with the wrong MAC address.
Web Page Reference Incompatible Master and Slave: A non-zero value indicates that the master and slave ends of the wireless link are different hardware products, or have different software versions. Note that it is very unusual to detect this because incompatible units will normally fail to establish a wireless link. However, some combinations may establish a partial wireless link and detect this situation. Note that a non-zero value may generate an SNMP trap and/or SMTP email alert.
Web Page Reference The page is subdivided into three main categories Equipment, Wireless and Ethernet/Internet. The ‘Equipment’ section contains the unit’s inventory and identification information. The ‘Wireless’ section presents the key wireless metrics, which are displayed as a series of measurements. The ‘Ethernet/Internet’ section describes the unit’s network identity and connectivity.
Web Page Reference Hardware Version: The hardware version attribute contains all the combined hardware version information. The attribute is formatted as DXX-RYY-Z where DXX contain the version of the digital card, RYY contains the version of the RF (radio frequency) card and Z describes the antenna type which can be I (integrated) or C (connectorized). Region Code: The region code is used by the system to constrain the wireless to operate within regulatory regime of the particular country.
Web Page Reference Receive Power: Receive power histogram is expressed in dBm and presented as: max, mean, min, and latest. The max, min and latest are true instantaneous measurements; the mean is the mean of a set of one second means. See footnote 10 “histograms”. Vector Error: The vector error measurement compares the received signal’s In phase / Quadrature (IQ) modulation characteristics to an ideal signal to determine the composite error vector magnitude.
Web Page Reference Receive Modulation Mode: The modulation mode currently being used on the receive channel. List of all the modulation modes can be found in Section 14 where data rate calculations plots are given for each available modulation mode. Receive Modulation Mode Detail: This supplies the user with information regarding the receive modulation mode in use.
Web Page Reference • Spectrum Management including DFS • Remote management • Diagnostics Plotter • Password Management • License Key Management • Properties • System Reboot 8.3.
Web Page Reference Figure 30 System Configuration Page While the majority of the system configuration is entered during installation and should never require changing, this page offers the system administrator the ability to change the basic system parameters for both the wireless and Ethernet components. Link Name: User defined identity for the unit (max 63 characters). Link Location: Can be used as a generic scratch pad to describe the location of the equipment.
Web Page Reference Why Reduce Transmit Power? If the link losses are low and the link data rate and availability targets are being easily achieved, the transmitted power level may be reduced with a consequent benefit to other users of the band, e.g. fixed satellite links. 8.3.1.2 LAN Configuration Page The LAN configuration page (Figure 31) is used by the system administrator to configure the 500 Series Bridge’s LAN interface. Figure 31 LAN Configuration Page IP Address: Internet protocol (IP) address.
Web Page Reference VLAN High Priority Traffic Threshold: All packets with an 802.1P priority tag greater than or equal to the indicated value will be treated as a high priority packet for transmission over the wireless link. Use VLAN For Management Interfaces: This controls whether the management interfaces (WWW/SNMP/SMTP/SNTP) use 802.1Q VLAN tags or not. See Section 8.3.1.3 “LAN Configuration Page - Use VLAN For Management Interface”.
Web Page Reference Figure 32 Configuration Reboot Page Figure 33 Configuration Reboot Page – Ethernet Auto Negotiation Disabled This will be followed by a pop-up dialogue box asking to confirm the action. Note: At this point you will lose connection to the unit. If you have just changed the IP Address you now have to reconnect to the unit using the address just set. 8.3.1.
Web Page Reference Caution: You must ensure that you can access the VLAN which you configure here, otherwise you will be unable to access the unit following the next reboot. Caution: The PTP 500 is only compatible with single VLAN tagged packets. Any packet with two or more tags will be ignored. Figure 34 VLAN Configuration Fields VLAN Management VID: This 802.1Q VLAN VID will be included in packets generated by the management interfaces. Valid settings are in the range 0 to 4094.
Web Page Reference 8.3.1.4 LAN Configuration Page – Manual Ethernet Configuration Figure 35 LAN Configuration Page – Manual Ethernet Configuration Force Configuration: This option allows the user to force the speed and duplex setting of the Ethernet interface.
Web Page Reference 8.3.1.5 Save and Restore Configuration File The save and restore feature of a PTP 500 Series Bridge allows the system administrator to backup the operation configuration of the wireless unit. It is recommended that this facility is used immediately after a successful PTP 500 Series Bridge installation or prior to any software upgrade. In the unlikely event that a unit has to be replaced in the field, the replacement unit can be reconfigured by simply playing back the saved configuration file.
Web Page Reference Figure 37 Save Configuration File Screen 74
Web Page Reference The configuration file is encoded using an ASCII encoding scheme. Figure 38. Figure 38 An example is show in PTP 500 Example Configuration File CAUTION: The configuration file is currently restricted to a single software version and can only be restored into a wireless unit operating the software version indicated in the configuration file header. The configuration file can also be used when swapping out a faulty wireless unit.
Web Page Reference Figure 39 Figure 40 Restore Configuration File Pop Up Screen Reset Configuration and Reboot Confirmation Pop-up 76
Web Page Reference On confirmation the PTP 500 Series Bridge will: • Upload the configuration file • Perform data integrity checking • Erase previous configuration • Apply the new configuration • Restart After the unit has restarted the entire configuration from the configuration file will now be active. Note: The IP address of the unit may have also been changed. The user can check the new IP address by reading the header of the configuration file, Figure 38.
Web Page Reference 8.3.2 Statistics Page The 500 Series bridge statistics page is designed to display some key statistics of the Ethernet Bridge and the underlying wireless performance. Figure 41 System Statistics Wireless Tx Packets: This displays the total number of good packets the bridge has sent for transmission by the wireless interface 16. Wireless Rx Packets: This displays the total number of good packets the bridge has received from the wireless interface. See footnote 16 “number of packets”.
Web Page Reference Ethernet Tx Packets: This displays the total number of good packets the bridge has sent for transmission by the local Ethernet interface. . See footnote 16 “number of packets”. Ethernet Rx Packets: This displays the total number of good packets the bridge has received from the local Ethernet interface. . See note See footnote 16 “number of packets”. Packets To Internal Stack: This displays the total number of good packets the bridge has transmitted to the internal stack (e.g.
Web Page Reference • Restricted because Installation is armed • Restricted because of byte errors on the wireless link • Restricted because a DFS channel change is in progress • Restricted due to the low Ethernet link speed • Limited by the radio conditions Signal Strength Ratio: The Signal Strength Ratio is the ratio of the power received by the Vertical / Horizontal receivers and presented as: max, mean, min, and latest in an histogram format.
Web Page Reference 8.3.3 Detailed Counters Page Figure 42 Detailed Counters Page The detailed counters page is subdivided into two columns. Column one presents the detailed statistics for the bridge’s Ethernet interface. Column two relates to the wireless interface. The Counters have the following definitions: Tx & Rx Octets: Total number of octets (bytes) transmitted or received over the interface. Rx Drops: Frames dropped due to lack of receive buffer.
Web Page Reference Rx CRC and Align: Total number of packets with CRC or frame alignment errors. Rx Undersize: Total number of packets received that are less than 64 bytes and have a valid CRC. Rx Oversize: Total number of packets received that are greater than the maximum number of bytes with a valid CRC. Rx Fragments: Total number of packets that are less than 64 bytes with an invalid CRC (these packet types are also known as runts).
Web Page Reference Example PTP 500 Series Configuration Data For your convenience these two units have been pre-configured as a link Units Units: ODU serial number ODU serial number 0167100000A0 016710000096 Ethernet MAC address Ethernet MAC address 00:04:56:10:00:96 00:04:56:10:00:A0 Configured as: Master Slave Target MAC address Target MAC address 00:04:56:10:00:A0 00:04:56:10:00:96 License key License Key 0557-D8B0-47A1-B0DD 534F-4F54-D1B0-E2DA IP Address IP Address 169.254.1.2 169.254.
Web Page Reference any other parameters require modification then it is recommended that the system administrator use the Installation Wizard. A detailed description of the Installation Wizard follows: The 500 Series bridge operational software requires a license key to enable the wireless bridging capability and programs region code specific parameters in to the unit.
Web Page Reference Figure 44 Installation Wizard Internet Protocol Configuration IP Address:Internet protocol (IP) address. This address is used by the family of Internet protocols to uniquely identify this unit on a network. Subnet Mask:A subnet allows the flow of network traffic between hosts to be segregated based on a network configuration. By organizing hosts into logical groups, subnetting can improve network security and performance.
Web Page Reference Figure 45 VLAN Warning Once complete, click the ‘Submit Internet Protocol Configuration’ button or the ‘Next’ link. 8.3.4.3 Wireless Configuration Step 2 of the installation wizard requires the installer to enter the wireless configuration parameters. Figure 46 5.8 GHz and 5.
Web Page Reference Target MAC Address:It is the MAC Address of the peer unit that will be at the other end of the wireless link. This is used by the system to ensure the unit establishes a wireless link to the correct peer. The MAC Address can be found embedded within the serial number of the unit. The last six characters of the serial number are the last three bytes of the unit’s MAC address. (Note: A PTP 500 Series system is shipped as a pair of units with pre-loaded correct MAC addresses.
Web Page Reference Depending upon the link characteristic that the customer requires, this may very well be the best choice. It increases consistency of link performance and equality in each direction as a trade-off against maximum throughput. Tx Max Power:This attribute controls the maximum transmit power the unit is permitted to use when installing and executing the wireless link. The maximum setting for a particular region or country is controlled by the License Key.
Web Page Reference Figure 47 5.8 GHz and 5.4 GHz Variants - Fixed Frequency Operation Installation Tones:Where the use of audio installation tones is not required this control allows the installer to optionally disable the tone generator during the installation process. Once the installer is satisfied with the wireless configuration options then the “Submit Wireless Configuration” button or the “Next” link should be clicked.
Web Page Reference Figure 48 5.8 GHz and 5.4 GHz Variants Installation Wizard Confirm Configuration If the settings are correct and appropriate, click the “Confirm Configuration, Arm Installation and Reboot” button. The user will now be prompted to confirm the action (Figure 49).
Web Page Reference Figure 49 Reboot Confirmation Pop Up All the attributes are committed to non-volatile memory. Immediately following the write to nonvolatile memory the unit is reset. Note: If you have changed the Ethernet parameters you must reconnect using the correct network and address settings.
Web Page Reference 8.3.4.4 Disarm Step 5 of the installation wizard is the disarm phase. Figure 50 5.8 GHz and 5.
Web Page Reference Once Section 8.3.4.3 “Wireless Configuration” is complete pressing the “Disarm Installation Agent” button completes the installation process 17 and the audible installation tone will be switched off. If the installer wishes to modify the installation configuration then the ‘Back’ link can be used to access the installation wizard steps described above. After disarming the wireless link the user is presented with one of two possible configuration pages, see Figure 52 and Figure 51.
Web Page Reference 8.3.5 Graphical Install To aid the installation of wireless links two graphical installation aids have been introduced in this 500 Series system version. • • A PDA installation screen A larger installation screen available from the main HTTP management interface. The design of the installation screen has been deliberately kept simple and uncluttered. An example of the installation screen is shown in Figure 53.
Web Page Reference 8.3.6 Software Upgrade The 500 Series system has two software image banks; one is a fixed image which is stored in protected non-volatile memory and cannot be modified by the user. The second bank is used by the system administrator to upgrade the firmware when necessary. Figure 54 shows the main software upgrade web page.
Web Page Reference The software image will now be uploaded to the unit. This upload should only take a few seconds. Once complete the image is verified and validated to ensure that no errors occurred during transfer and that the image is valid to run on the current platform. If there are any problems a warning screen will appear. The unit being upgraded will now display information about the build it currently has stored in the image bank and the one that’s just been uploaded.
Web Page Reference Figure 56 Software Download Progress Indicator Figure 57 Software Upgrade Complete When the software image has been written to non-volatile memory Figure 57 will be displayed showing the status of the software upload. Reboot the unit by clicking the “Reboot Wireless Unit” button. You will be asked to confirm this action as shown in Figure 58. Figure 58 Reboot Confirmation Pop Up This will reboot the unit, taking up to 120 seconds.
Web Page Reference If you cannot communicate with the unit after 120 seconds, this could indicate a problem with the memory update process. Under these circumstances the user should enter “Recovery Mode”, see Section 9 “Recovery Mode”. After the reboot the user should check that the required software image is loaded and running. NOTE: Please ensure that you are upgrading the correct units. Units cannot be downgraded.. 8.3.
Web Page Reference • Peak of Means • 99.9% Percentile of the Means • Mean of Means Peak of Means:is the largest mean interference measurement encountered during the quantization period. The peak of means is similar to the peak of peaks and is useful for detecting slightly longer duration spikes in the interference environment. 99.9% Percentile of the Means is the value of mean interference measurement which 99.9% of all mean measurements fall below, during the quantization period. The 99.
Web Page Reference Figure 59 Spectrum Management as seen from the Master 100
Web Page Reference Figure 60 Spectrum Management as seen from the Slave Figure 59 shows an example Spectrum Management webpage as seen from the master. Figure 60 shows an example Spectrum Management webpage as seen from the slave. It should be noted that the key configuration attributes are not available on the slave web page. 8.3.7.5 Spectrum Management Configuration The following section describes the user modifiable configuration accessible from the Spectrum Management webpage.
Web Page Reference Hopping Margin:Spectrum Management uses this margin when making a channel hop decision. The target channel has to have an interference level 3 dB (default) better than the current active channel. Hopping Period (not configurable):The Spectrum Management algorithm evaluates the metrics every ‘Hopping Period’ seconds (180 seconds by default) looking for a channel with lower levels of interference. If a better channel is located, Spectrum Management performs an automated channel hop.
Web Page Reference Figure 61 Example Spectrum Management Graphic The X-axis shows a stylized view of the selectable wireless channels. It is important to note that adjacent channels on the display have a 10 MHz overlap. The display separates the display of channels to help the clarity of the resultant display. The axis is labeled using the channel center frequencies in MHz. The Y-axis shows the interference power levels from -100 to -40 dBm.
Web Page Reference Green Active The channel is currently in use, hosting the Point-to-Point wireless link. Orange Interference The channel has interference above the intererence threshold Blue Available The channel has an interference level below the interference threshold and is considered by the Spectrum Management algorithm suitable for hosting the Point-to-Point link. Grey Barred The system administrator has barred this channel from use.
Web Page Reference 8.3.7.9 Viewing Historic Spectrum Management Metrics Spectrum Management allows the system administrator to view the results of previous measurement quantization periods. Holding down the shift key and clicking the appropriate channel on the local channel spectrum plots activates this feature. This feature is available on both the master and slave web page. Figure 63 Spectrum Management Time Series Plot Figure 63 shows an example time series plot.
Web Page Reference Figure 64 Spectrum Management Fixed Frequency Screen Channel barring is disabled in fixed frequency mode; it is not required as dynamic channel hopping is prohibited in this mode. The only controls available to the master are the Statistics Window and Interference Threshold attributes. They will have no effect on the operation of the wireless link and will only effect the generation of the channel spectrum graphics.
Web Page Reference Figure 65 Spectrum Management Help Page (Fixed Frequency) 8.3.9 Spectrum Management Control – With Operational Restrictions When operating with Radar Avoidance enabled the following variances in operation apply: • The words “Radar Avoidance” are appended to the “Spectrum Management” title at the top of the screen. See Figure 66 and Figure 67. • The only controls available to the master are the Interference Threshold attribute.
Web Page Reference Figure 66 Spectrum Management Master Screen With Operational Restrictions 108
Web Page Reference Figure 67 Spectrum Management Slave Screen With Operational Restrictions The colored bar represents the following channel state: 109
Web Page Reference Green Active The channel is currently in use hosting the Point-to-Point wireless link Orange Interference The channel has interference above the interference threshold Blue Available The channel has an interference level below the interference threshold and is considered by the Spectrum Management algorithm suitable for hosting the Point-to-Point link Grey Barred The system administrator has barred this channel from use.
Web Page Reference 8.3.10 Remote Management Page The Remote Management page (Figure 68) allows the system administrator to configure the remote management of the PTP 500 Series Bridge. 8.3.10.1 Control Access to HTTP Interface The attribute HTTP Access Enabled allows a user to stop any access to a unit via the web interface. The default value for this control is set to “yes”, which means that the unit can be accessed using the web interface.
Web Page Reference 112 Figure 68 Remote Management
Web Page Reference Figure 69 Warning when disabling HTTP Interface 8.3.10.5 Diagnostics Alarms A number of diagnostics alarms have been added to allow SNMP agents to receive traps and emails if required. Refer to Section 8.1.1 “Home Page Alarm Display” for a description of all these alarms. Checking the control “Enabled Diagnostic Alarms” in SNMP and/or SNTP selects all the alarms shown in Figure 70. Users can access the sub-menu “Diagnostic Alarms” to modify the alarms selected.
Web Page Reference Figure 70 Remote Management – Diagnostic Alarms For a copy of the Motorola proprietary version 1 and version 2 MIB RFCs please consult the installation CD 8.3.10.6 SNMP Configuration SNMP State:The SNMP state attribute controls the creation of the SNMP features. Changing the SNMP state attribute requires a mandatory reboot of the unit. Only when the SNMP state is enabled at system start-up will the SNMP processor task be created.
Web Page Reference SNMP Community String:The SNMP community string acts like a password between the networks SNMP management entity and the distributed SNMP clients (600 Series bridge). Only if the community string is configured correctly on all SNMP entities can the flow of management information take place. By convention the default value is set to ‘public’. When the community string is changed the system requires a mandatory reboot before the new string or phrase is adopted.
Web Page Reference SNTP IP Address:The IP Address of the networked SNTP Server. SNTP Port Number:The port number of the networked SNTP server. By convention the default value for the port number is 123. SNTP Poll Interval:The period at which the SNTP client polls the server for time correction updates. Default 1 hour. If for any reason an SNTP poll fails, the client will automatically perform 3 retries before waiting for the user defined poll period.
Web Page Reference For example, when histogram 1 fills up and starts to overflow the first minute of overflow is analyzed and the maximum, minimum and mean over that minute are computed and inserted into histogram 2. When histogram 2 fills up and starts to overflow the first hour of overflow is analyzed and the maximum, minimum and mean over that hour is computed and inserted into histogram 3. When histogram 3 starts to overflow, the overflow data is simply discarded. 8.3.11.
Web Page Reference • Tx Data Rate • Aggregate Data Rate The diagnostic plotter uses a novel time representation in the x-axis which compresses the timeline of the plot without sacrificing resolution. The trace selection allows the user to control which traces are plotted. As with other management pages the page refresh period can be used to interactively monitor the wireless link. 8.3.11.
Web Page Reference 255784 entries comprises 3600 entries for the first hour, 1440 entries for the next 24 hours and 744 entries for the next 31 days. 8.3.12 Change System Administration Password This page (Figure 73) is used to change the password for the system administration (The factory default is blank). Figure 73 Password Change To change the password any combination of alphanumeric characters, up to 31 characters in length, can be used. 8.3.
Web Page Reference Figure 74 Software License Key Data Entry The user must enter the license key and click the ‘Validate License Key’ button to check that the key is valid and program it to non-volatile memory. If a valid license key is detected then the user will be presented by a system reboot screen. Figure 75 License Key reboot Screen The user will then be asked to confirm the reboot (Figure 76).
Web Page Reference Figure 76 Reboot Confirmation Pop Up 8.3.14 Properties The web page properties screen allows the user to configure the web page interface. Figure 77 Properties WEB Properties:Disable Front Page Login. Allows access to homepage and status page web pages without forcing a login as the system administrator. WEB Properties:Disable HTTP NO-CACHE META data. Removes the HTTP NO-CACHE META clause from all dynamically created web pages.
Web Page Reference 8.3.15 Reboot The reboot page allows the system administrator to perform commanded reboots of the wireless unit. The reboot page also allows the system administrator to view a list of past reboot reasons. The “Previous Reasons For Reset/Reboot” field has been implemented as a drop down selection box, where the latest reason for reboot is located at the top of the list.
Recovery Mode 9 Recovery Mode The Motorola PTP 500 point-to-point wireless Ethernet bridges have a special mode of operation that allows the user to recover a unit from configuration errors or software image corruption. Recovery mode is entered by depressing the Recovery Switch located on the underside of the PIDU Plus while applying mains power, as shown in Section 3.3.2 “PIDU Plus - PTP 500 Series Bridge”.
Recovery Mode Figure 81 Recovery Options Page The recovery options available are: Upgrade Software Image:This allows the user to reload a software image. This may be the original image if software corruption is suspected or a step back to an old image if an incorrect image has just been loaded. Reset IP and Ethernet Configuration back to factory defaults:This allows the user to reset the unit back to the factory defaults: • IP Address 169.254.1.1 (or 10.10.10.10) • Netmask 255.255.0.0 • Gateway 169.
Recovery Mode Recovery Reason:Indicates the reason the unit is operating in Recovery mode. Possible reasons are “Recovery button active” or “Invalid or corrupt image” MAC Address:The MAC address shown here is the MAC address of the unit programmed during manufacture. 9.1 Upgrade Software Image The first step (Figure 81) is to use the ‘Browse’ button to locate the software image to be downloaded. Once located the user should press the “Upgrade Software Image” button to start the software download process.
Recovery Mode Figure 84 Reboot Confirmation Pop Up 9.2 Reset IP and Ethernet Configuration To reset IP and Ethernet configuration back to factory defaults the user should press the “Reset IP and Ethernet Configuration back to factory defaults” button on the “Recovery Options” page (Figure 81). The user will now be presented with a pop up box asking them to confirm the action (Figure 85). Figure 85 Confirm Reset to Factory Default Pop Up On confirmation the following page will be displayed (Figure 84).
Recovery Mode Figure 86 IP and Ethernet Erased Successfully page The user will now be presented with a pop up box asking them to confirm the action Figure 87. Figure 87 Reboot Confirmation Pop Up The unit will now reboot. The unit should now start up in normal mode but with the IP address set to 169.254.1.1 and the Ethernet interface set to auto-negotiate and auto-MDI/MDIX. Should the unit fail to start up the user should refer to Section 10 “Fault Finding”.
Recovery Mode 9.3 Erase Configuration To erase the unit’s configuration the user should press the “Erase Configuration” button on the “Recovery Options” page (Figure 81). The user will now be presented with a pop up box asking them to confirm the action (Figure 88). Figure 88 Confirm Erase Configuration Pop Up On confirmation the following page will be displayed (Figure 89). The user should now reboot the unit by pressing the “Reboot” button.
Recovery Mode Figure 89 Erase Configuration Successful Page The user will now be presented with a pop up box asking them to confirm the action Figure 90. Figure 90 Erase Configuration – Reboot Confirmation Pop Up The unit will now reboot. The unit should now start up in normal mode but with all configuration erased. Should the unit fail to start up the user should refer to Section 10 “Fault Finding”.
Recovery Mode 9.4 Erase Security Parameters To erase the unit’s security parameters and to comply with FIPS the user should press the “Zeroise Critical Security Parameters” button on the “Recovery Options” page (Figure 81). The user will now be presented with a pop up box asking them to confirm the action (Figure 91). Figure 91 Confirm Zeroise Security Parameters Pop Up On confirmation the following page will be displayed (Figure 92).
Recovery Mode Figure 92 Zeroise Parameters Successful Page 9.5 Reboot This option can be used to reboot the unit. The user will now be presented with a pop up box asking them to confirm the action (Figure 93). Figure 93 Recovery – Reboot Confirmation Pop Up The unit will now reboot. The unit should now start up in normal operational mode. Should the unit fail to start up the user should refer to Section 10 “Fault Finding”.
Fault Finding 10 Fault Finding If communication has been lost with the unit at the near end of the link then there may be a hardware fault with the wiring, network or hardware. Go to the hardware section below. If communication with the far end of the link is lost then go to the radio section below. 10.1 Hardware If there are problems suspected with the link hardware the following procedure is recommended. 10.1.1 Power Check the power LED at each end of the link.
Fault Finding Differentiating between 1-3 and 4 can be achieved by removing the power for 1 second. Watch the Ethernet indicator for 1 minute while power is removed, if it never flashes then the problem is 1-3. Take the jumper (J905) out of the PIDU Plus and check the current taken by the ODU. This should be 300mA to 1A when starting to run normally.
Fault Finding 3. Check the cable resistance between pins 1 & 3 at the RJ45. Check against column 3 in Table 17. 4. Check the cable resistance between pins 4 & 7 at the RJ45. Check against column 4 in Table 17. 5. Ensure that there is greater than 100K ohms between pins 1 & 8 for all cable lengths. 6. Ensure that there is greater than 100K ohms between pin 1 and ODU ground for all cable lengths. 7. Ensure that there is greater than 100K ohms between pin 8 and ODU ground for all cable lengths 10.2 Radio 10.
Lightning Protection 11 Lightning Protection EMD (Lightning) damage is not covered under standard warranty The recommendations in this user manual when installed correctly give the user the best protection from the harmful effects of EMD. However 100% protection is neither implied nor possible. 11.1 Overview The idea of lightning protection is to protect structures, equipment and people against lightning by conducting the lightning current to ground via a separate preferential solid path.
Lightning Protection Figure 94 ODU mounted in Zones A and B Figure 95 Showing how the use of a Finial enables the ODU to be mounted inside Zone B 136
Lightning Protection Zone A Zone B Earth ODU Mandatory Mandatory Screen Cable Mandatory Mandatory Lightning protection Unit at ODU - PTP-LPU Mandatory Mandatory Earth Cable at Building Entry Mandatory Mandatory Lightning protection Unit at Building Entry - PTP-LPU Mandatory Mandatory Table 16 Protection Requirements 11.2 Detailed Installation The recommended components for an installation protected for nearby strikes are: • Recommended cables as described in Section 3.3.5.
Lightning Protection Figure 96 Diagrammatically Showing Typical Mast and Wall Installations The Lightning protection Unit should be mounted at the building entry point and must be grounded. Figure 97 shows all the components that are supplied with the Motorola Kit 2978.
Lightning Protection 11.
Lightning Protection 11.3.1 Pre-Power Testing Before plugging the RJ45 from the lower LPU (or if not fitted the ODU) into the PIDU, check the following resistances at the RJ45: 1. Check the cable resistance between pins 1&2, 3&6, 4&5 and 7&8 at the RJ45. Check against column 2 in Table 17. Resistances for each pair should be within 1 ohm of each other. 2. Check the cable resistance between pins 1&3 and 4&7 at the RJ45. Check against columns 3 and 4 respectively in Table 17. 3.
Lightning Protection 1. Connect the RJ45 to the PIDU and apply power to the PIDU, the power LED should illuminate continuously. 2. 30 seconds after powering, the Ethernet LED should be observed starting with 10 slow flashes. 3. If there is a network connection the Ethernet LED will then show Ethernet activity. If the system does not operate corrctly, refer to the fault finding below. The PIDU Green power LED does not illuminateUnplug the ODU connection from the PIDU and check the power LED illumination.
Lightning Protection 11.4 Locating the Fault Having identified which of the wiring cores are likely to be connected incorrectly, the location of the faulty cable can be narrowed by disconnecting sections of the drop cable and by unplugging the relevant RJ45 connectors from the LPUs. As a further aid to locating the fault the Ethernet connections are also available inside the LPU.
Wind Loading 12 Wind Loading 12.1 General Antennas and electronic equipment mounted on towers or pole mounted on buildings will subject the mounting structure to significant lateral forces when there is appreciable wind. Antennas are normally specified by the amount of force (in pounds) for specific wind strengths. The magnitude of the force depends on both the wind strength and size of the antenna. 12.
Wind Loading Note: When the connectorized version of 500 Series bridge is used with external antennas, the figures from the antenna manufacturer for lateral force should be included to calculate to total loading on the mounting structure. 12.3 Capabilities of the PTP 500 Series Bridges The structure and mounting brackets of the PTP Series systems are capable of withstanding wind speeds up to 151mph (242 kph).
PTP 500 Series Bridge - Connectorized Model 13 PTP 500 Series Bridge - Connectorized Model 13.1 Scope This section details the changes and additional features relevant to the connectorized version of the PTP 500 Series products.. 13.2 Product Description 13.2.
PTP 500 Series Bridge - Connectorized Model In non-FCC regions antenna choice is not restricted but any region specific EIRP limit must be obeyed by reducing the maximum Transmit power 23, see Table 6 in Section 5.2 “Region Codes”. In FCC regions external antennas from the list in Section 13.6.3 “Antennas for USA / Canada – 5.8 GHz” can be used with the Connectorized version of the 500 Series Bridge.
PTP 500 Series Bridge - Connectorized Model Figure 101 Connectorized 500 Series bridge Status Page 13.3.2 Configuration Pages The amended Configuration web page is shown below as Figure 102. Please refer to Section 8.3.4 for the definitions of the parameters Antenna Gain, Cable Loss and EIRP.
PTP 500 Series Bridge - Connectorized Model 13.3.3 Installation Pages The installer is prompted to enter the Antenna Gain and Cable Loss (Connectorized PTP 500 Series Bridge to antenna) at each end of the link. The Installation Page(s) is shown as Figure 103 to Figure 105. Figure 103 Connectorized PTP 500 Series Bridge ‘Installation Wizard’ Page Antenna Gain:Gain of the antenna you are connecting to the unit, see table in Section 13.2.3 “Antenna Choices – 5.4 GHz”.
PTP 500 Series Bridge - Connectorized Model Spectrum Management Control:Is used to configure the 500 Series Bridge Spectrum Management features, see Section 8.3.7 for more details. iDFS is the abbreviation for intelligent Dynamic Frequency Selection, which continually monitors the spectrum looking for the channel with the lowest level of on channel and co-channel interference. Fixed frequency mode allows the installer to fix the Transmit and receive frequencies on the units.
PTP 500 Series Bridge - Connectorized Model EIRP:The Confirm Installation Page displays the EIRP (Effective Isotropic Radiated Power), which describes the strength of the radio signal leaving the wireless unit. This allows the operator to verify that their link configuration (Max Transmit Power, Antenna Gain and Cable Loss) do not cause the link to exceed any applicable regulatory limit. Figure 105 Connectorized 500 Series bridge ‘Disarm Installation’ Page 13.
PTP 500 Series Bridge - Connectorized Model specific link – for example when the link is heavily obscured by dense woodland on an NLOS link or extremely long LOS links (>80km or >50 miles) over water. The external antennas can be either dual-polarization (as the integrated antenna) or two single polarized antennas can be used in a spatially diverse configuration.
PTP 500 Series Bridge - Connectorized Model 13.6.2 Cable Losses (FCC Regions Only) The FCC approval for the product is based on tests with a cable loss between the units of approximately 1.2dB at 5.8GHz. The use of lower cable losses would result in the installation being outside the FCC rules. As an indication, 1.2dB of cable loss corresponds to the following cable lengths excluding connector losses (source: Times Microwave). Cable Length for 1.2dB Cable Loss at 5.8GHz (ft) (m) LMR100 1.9 0.
PTP 500 Series Bridge - Connectorized Model 13.6.3 Antennas for USA / Canada – 5.8 GHz Manufacturer Antenna Type Gain Flat Parabolic (dBi) Plate Dish Andrew Andrew 1-foot Flat Panel, FPA5250D12-N (23.6dBi) 23.6 Y Andrew Andrew 2-foot Flat Panel, FPA5250D24-N (28dBi) 28 Y Gabriel Gabriel 1-foot Flat Panel, DFPD1-52 (23.5dBi) 23.
PTP 500 Series Bridge - Connectorized Model Manufacturer Antenna Type Gain Flat Parabolic (dBi) Plate Dish Gabriel Gabriel 2-foot High Performance QuickFire Parabolic, HQF2-52-N 28.2 Y Gabriel Gabriel 4-foot High Performance QuickFire Parabolic, HQF4-52-N 34.4 Y Gabriel Gabriel 6-foot High Performance QuickFire Parabolic, HQF6-52-N 37.4 Y Gabriel Gabriel 2-foot High Performance Dual QuickFire Parabolic, HQFD2-52-N 28.
PTP 500 Series Bridge - Connectorized Model Manufacturer Antenna Type Gain Flat Parabolic (dBi) Plate Dish Gabriel Gabriel 4-foot Standard Dual QuickFire Parabolic, QFD4-52-N-RK 34.7 Y Gabriel Gabriel 6-foot Standard Dual QuickFire Parabolic, QFD6-52-N 37.7 Y RadioWaves Radio Waves 2-foot Dual-Pol Parabolic, SPD2-5.2 (28.1dBi) 28.1 Y RadioWaves Radio Waves 2-foot Parabolic, SP2-5.2 (29.0dBi) 29 Y RadioWaves Radio Waves 3-foot Dual-Pol Parabolic, SPD3-5.2 (31.1dBi) 31.
PTP 500 Series Bridge - Connectorized Model Manufacturer Antenna Type Gain Flat Parabolic (dBi) Plate Dish RFS RFS 4-foot Parabolic, SPF4-52AN or SPFX4-52AN(33.9dBi) 33.9 Y RFS RFS 6-foot Parabolic, SPF6-52AN or SPFX6-52AN (37.4dBi) 37.4 Y RFS RFS 2-foot HP Parabolic, SDF2-52AN or SDFX2-52AN (31.4dBi) 31.4 Y RFS RFS 4-foot HP Parabolic, SDF4-52AN or SDFX4-52AN (33.9dBi) 33.9 Y RFS RFS 6-foot HP Parabolic, SDF6-52AN or SDFX6-52AN (37.4dBi) 37.
PTP 500 Series Bridge - Connectorized Model 13.6.4 Antennas for USA / Canada – 5.4 GHz Manufacturer Antenna Type Gain Parabolic (dBi) Dish Andrew Andrew 2-foot Parabolic, P2F-52 (29.4dBi) 29.4 Y Andrew Andrew 2-foot Dual-Pol Parabolic, PX2F-52 (29.4dBi) 29.4 Y Andrew Andrew 3-foot Parabolic, P3F-52 (33.4dBi) 33.4 Y Andrew Andrew 3-foot Dual-Pol Parabolic, P3F-52 (33.4dBi) 33.4 Y Andrew Andrew 4-foot Parabolic, P4F-52 (34.9dBi) 34.
PTP 500 Series Bridge - Connectorized Model Manufacturer Antenna Type Gain Parabolic (dBi) Dish Gabriel Gabriel 4-foot Standard Dual QuickFire Parabolic, QFD4-52-N-RK 34.7 Y RadioWaves Radio Waves 2-foot Dual-Pol Parabolic, SPD2-5.2 (28.1dBi) 28.1 Y RadioWaves Radio Waves 2-foot Parabolic, SP2-5.2 (29.0dBi) 29 Y RadioWaves Radio Waves 3-foot Dual-Pol Parabolic, SPD3-5.2 (31.1dBi) 31.1 Y RadioWaves Radio Waves 3-foot Parabolic, SP3-5.2 (31.4dBi) 31.
PTP 500 Series Bridge - Connectorized Model 500 Series bridge. The main selection criteria will be the required antenna gain. The secondary criteria should be the ease of mounting and alignment. For example the Radio Waves Parabolic dishes are supplied with a mount that allows adjustment for alignment independent of the actual antenna mounting. This type of antenna is much easier to align than those that have to be rotated around the mounting pole for alignment. 13.7.
PTP 500 Series Bridge - Connectorized Model 13.7.6 Mounting the antennas The Antennas should be mounted according to the manufacturer’s instructions. Actual antenna position will depend on the available mounting positions and link requirements. It may be necessary to mount the antennas 20m apart or at a certain distance from the ground to get the desired results. 13.7.
PTP 500 Series Bridge - Connectorized Model 13.7.10 Completing the Installation The installation should be completed by checking all mounting nuts bolts and screws, securing all cables and weatherproofing the installation. Warning: Finally tightening the antenna mountings may cause the antenna alignment to be altered, due to distortion in the mounting bracket caused by action of tightening.
PTP 500 Series Bridge - Connectorized Model Figure 107 Weatherproofing the Antenna Connections 13.8 Additional Lightning Protection The following guidelines should be applied in addition to those described in Section 11 ”Lightning Protection”. 13.8.1 ODU Mounted Outdoors Where the ODU is mounted outdoors and is mounted some distance from the antenna, it is advisable to add additional grounding by utilizing Andrew Assemblies (such as Andrew Type 223158 www.andrew.com) as shown in Figure 108.
PTP 500 Series Bridge - Connectorized Model 13.8.2 ODU Mounted Indoors Where the ODU is mounted indoors, lightning arrestors should be deployed where the antenna cables enter the building as shown in Figure 109. Figure 109 Lightning Arrestor Mounting The lighting arrestors should be ground bonded to the building ground at the point of entry. Motorola recommends Polyphaser LSXL-ME or LSXL lighting arrestors. These should be assembled as show in Figure 110.
Data Rate Calculations 14 Data Rate Calculations To aid the calculation of data rate throughput, the following plots of throughput verses link range have been produced for all the PTP 500 Series modulation modes, assuming the units are connected using 100 Mbps Ethernet. Please note that only 15 MHz channel bandwidth has been considered and the plots are the same for IP or TDM modes.
Data Rate Calculations Figure 112 QPSK 0.50 Single Payload Figure 113 QPSK 0.
Data Rate Calculations Figure 114 16 QAM 0.50 Single Payload Figure 115 16 QAM 0.
Data Rate Calculations Figure 116 64 QAM 0.67 Single Payload Figure 117 64 QAM 0.
Data Rate Calculations Figure 118 256 QAM 0.75 Single Payload Figure 119 QPSK 0.
Data Rate Calculations Figure 120 QPSK 0.75 Dual Payload Figure 121 16 QAM 0.
Data Rate Calculations Figure 122 16 QAM 0.75 Dual Payload Figure 123 64 QAM 0.
Data Rate Calculations Figure 124 64 QAM 0.83 Dual Payload Figure 125 256 QAM 0.
AES Encryption Upgrade 15 AES Encryption Upgrade The Motorola PTP 500 Series bridges support link encryption using the NIST approved Advanced Encryption Standard, HFIPS-197 UTH. This standard specifies AES (Rijndael) as a FIPS-approved symmetric encryption algorithm that may be used by U.S. Government organizations (and others) to protect sensitive information. Link Encryption is not available in the standard PTP 500 Series system.
AES Encryption Upgrade Figure 126 AES Software License Key Data Entry 4. When both license keys have been successfully validated confirm the reboot for both ends of the link. The software is designed to allow five seconds so that a user can command both ends of the link to reset before the wireless link drops. 5. The link will automatically re-establish. 15.1.2 Encryption Mode and Key Entering the license keys only does not initialize AES link encryption.
AES Encryption Upgrade Figure 127 AES Configuration Data Entry Page Motorola recommends the following process for entering AES link encryption configuration:1. Open two browsers, one for each end of the link 2. Navigate to the ‘Configuration’ data entry page for each end of the link 3. At both ends of the link select the ‘AES (Rijndael)’ Encryption Algorithm required. 4. At both ends of the link enter ether an 128-bit or 256-bit encryption key.
AES Encryption Upgrade 5. Submit configuration on both ends of the link, but do not reboot. 6. Reboot both ends of the link Figure 128. The software is designed to allow five seconds so that a user can command both ends of the link to reboot before the wireless link drops. Figure 128 Configuration Reboot Screen 15.2 Wireless Link Encryption FAQ 15.2.1 Encryption data entry fields are not available Check that the correct license key has been inserted into the unit.
Legal and Regulatory Notices 16 Legal and Regulatory Notices 16.1 Important Note on Modifications Intentional or unintentional changes or modifications to the equipment must not be made unless under the express consent of the party responsible for compliance. Any such modifications could void the user’s authority to operate the equipment and will void the manufacturer’s warranty. 16.2 National and Regional Regulatory Notices – 5.8 GHz variant 19.2.1 U.S.
Legal and Regulatory Notices Where necessary, the end user is responsible for obtaining any National licenses required to operate this product and these must be obtained before using the product in any particular country. Contact the appropriate national administrations for details on the conditions of use for the bands in question and any exceptions that might apply. Also see http://www.ero.dk for further information. 16.2.1 European Union Notification The 5.
Legal and Regulatory Notices by the WEEE directive, this cross-out trash bin label means that customers and end-users in EU countries should not dispose of electronic and electrical equipment or accessories in household waste. Customers or end-users in EU countries should contact their local equipment supplier representative or service center for information about the waste collection system in their country. 16.2.2 UK Notification The 5.
Legal and Regulatory Notices • • • • Increase the separation between the affected equipment and the unit; Connect the affected equipment to a power outlet on a different circuit from that which the receiver is connected to; Consult the dealer and/or experienced radio/TV technician for help.
Legal and Regulatory Notices not dispose of electronic and electrical equipment or accessories in household waste. Customers or end-users in EU countries should contact their local equipment supplier representative or service center for information about the waste collection system in their country. 16.4 Exposure See Section 2 “Avoiding Hazards”. 16.5 Legal Notices 16.5.1 Motorola Inc.
Legal and Regulatory Notices 1. Only you, your employees or agents may use the Software and Documentation. You will take all necessary steps to insure that your employees and agents abide by the terms of this Agreement. 2. You will use the Software and Documentation (i) only for your internal business purposes; (ii) only as described in the Software and Documentation; and (iii) in strict accordance with this Agreement. 3.
Legal and Regulatory Notices 16.5.1.5 Confidentiality You acknowledge that all Software and Documentation contain valuable proprietary information and trade secrets and that unauthorized or improper use of the Software and Documentation will result in irreparable harm to Motorola for which monetary damages would be inadequate and for which Motorola will be entitled to immediate injunctive relief.
Legal and Regulatory Notices 16.5.1.10 Disclaimer MOTOROLA DISCLAIMS ALL WARRANTIES OF ANY KIND, WHETHER EXPRESS, IMPLIED, STATUTORY, OR IN ANY COMMUNICATION WITH YOU. MOTOROLA SPECIFICALLY DISCLAIMS ANY WARRANTY INCLUDING THE IMPLIED WARRANTIES OF MERCHANTABILTY, NONINFRINGEMENT, OR FITNESS FOR A PARTICULAR PURPOSE. THE SOFTWARE AND DOCUMENTATION ARE PROVIDED “AS IS.
Legal and Regulatory Notices been destroyed, except that, with prior written consent from Motorola, you may retain one copy for archival or backup purposes. You may not sublicense, assign or transfer the license or the Product, except as expressly provided in this Agreement. Any attempt to otherwise sublicense, assign or transfer any of the rights, duties or obligations hereunder is null and void. 16.5.1.
Legal and Regulatory Notices OR PERFORMANCE OF THIS SOFTWARE. ONLY OPEN THE PACKAGE, OR USE THE SOFTWARE AND RELATED PRODUCT IF YOU ACCEPT THE TERMS OF THIS LICENSE. BY BREAKING THE SEAL ON THIS DISK KIT / CDROM, OR IF YOU USE THE SOFTWARE OR RELATED PRODUCT, YOU ACCEPT THE TERMS OF THIS LICENSE AGREEMENT. IF YOU DO NOT AGREE TO THESE TERMS, DO NOT USE THE SOFTWARE OR RELATED PRODUCT; INSTEAD, RETURN THE SOFTWARE TO PLACE OF PURCHASE FOR A FULL REFUND.
Legal and Regulatory Notices − The origin of this software must not be misrepresented; you must not claim that you wrote the original software. If you use this software in a product, an acknowledgment in the product documentation would be appreciated but is not required. − Altered source versions must be plainly marked as such, and must not be misrepresented as being the original software. − This notice may not be removed or altered from any source distribution. Jean-loup Gailly jloup@gzip.
Specifications 17 Specifications 17.1 System Specifications 17.1.1 Wireless 5.4GHz Variant Radio Technology Specification RF Band 5.470-5.725GHz Channel Selection By dynamic frequency control and manual intervention. Automatic detection on start-up and continual adaptation to avoid interference. Dynamic Frequency Control Initial capture 10-15 sec. Out of service on interference 100 ms.
Specifications 17.1.2 Wireless 5.8GHz Variant Radio Technology Specification RF Band 5.725-5.850GHz Channel Selection By dynamic frequency control and manual intervention. Automatic detection on start-up and continual adaptation to avoid interference. Dynamic Frequency Control Initial capture 10-15 sec. Out of service on interference 100 ms.
Specifications 17.1.3 Management Management Specification Status Indication Power status Ethernet Link Status Data activity Installation Web server and browser for setup Audio tone feedback during installation , plus graphical installation tool suitable for laptop and PDA computing devices Web server for confirmation Radio Performance and Management Via web server and browser, SNMP Alarms Via configurable email alerts, SNMP 17.1.4 Ethernet Bridging Ethernet Bridging Specification Protocol IEEE802.
Specifications 17.1.5 Physical Integrated Specification Dimensions Width 14.5” (370mm), Height 14.5” (370mm), Depth 3.75” (95mm) Weight 12.1 lbs (5.5 Kg) including bracket Connectorized Specification Dimensions Width 12” (305mm), Height 12” (305mm), Depth 4.01” (105mm) Weight 9.1 lbs (4.3 Kg) including bracket 17.1.6 Powering Power Supply Separate power supply unit (included) Dimensions Width 9.75” (250mm), Height 1.5” (40mm), Depth 3” (80mm) Weight 1.9 lbs (0.
Specifications Region Specification USA FCC Part 15 Class B Canada CSA Std C108.8, 1993 Class B Europe EN55022 CISPR 22 17.4 EMC Immunity Compliance Top-level Specification ETSI 301-489.
Specifications 17.5.2 Radio Certifications - 5.8 GHz Variant Region Specification (Type Approvals) USA FCC Part 15.247 Canada RSS 210 Issue 7 UK IR 2007 Eire Comreg 03/42 17.6 Environmental Specifications Category Specification Temperature ODU -40◦ F (-40◦ C) to 140◦ F (+60◦ C) PIDU Plus (indoor) 32◦ F (0◦ C) to 104◦ F (+40◦ C) PIDU Plus (outdoor)-40◦ F (-40◦ C) to 140◦ F (+60◦ C) Wind Loading 150mph Max (242 kmh).
Specifications 17.7 System Connections 17.7.
FAQs 18 FAQs Can I source and use my own PoE adaptor with the 500 Series bridge? No. The 500 Series bridge uses a non-standard PoE configuration. Failure to use the Motorola supplied Power Indoor Unit could result in equipment damage and will invalidate the safety certification and may cause a safety hazard. Why has Motorola launched the 500 Series bridge? The 500 Series bridge is the first product to feature Multiple-Input Multiple-Output (MIMO).
FAQs that is clear of interference. In operation 500 Series bridge continuously monitors the spectrum to ensure it is operating on the cleanest channel. How does the 500 Series bridge integrate into my data network?The 500 Series bridge acts as a transparent bridge between two segments of your network. In this sense, it can be treated like a virtual wired connection between the two buildings. The 500 Series bridge forwards 802.
Glossary 19 Glossary AES ARP ARQ BPSK CAC DC DFS EIRP EMD ETSI FAQ FCC GPS HTTP ID IEEE i-DFS IP IQ ISM ITU LAN LED LPU MAC MDI MDIX MIMO NIST NLOS ODU OFDM PC PIDU+ PING PoE PSU PTP QAM RAM RTTT STC STP TCP TPC URL USA Advanced Encryption Standard Address Resolution Protocol Automatic Repeat reQuest Binary Phase Shift Keying Channel Availability Check Direct Current Multiplex Dynamic Frequency Selection Equivalent Isotropically Radiated Power Earth Movers Distance European Telecommunications Standards In
Glossary UTP VLAN Unshielded Twisted Pair Virtual Local Area Network 197
Unit A1, Linhay Business Park Eastern Road, Ashburton Devon, TQ13 7UP, UK Telephone Support: +1 877 515-0400 (Worldwide) +44 803 234 4640 (UK) www.motorola.com/ptp Motorola, the stylized M Logo and all other trademarks indicated as such herein are trademarks of Motorola, Inc. Reg. US Pat & TM. Office. All other C 2008 product or service names are the property of their respective owners. Motorola, Inc.