10 Lightning Protection
224
10.2 Detailed Installation
The PTP LPU can be installed in one of the following configurations:
Option 1: Back-to-Back with the ODU using the supplied brackets delivered part of the
installation of a link. This is the configuration recommended by Motorola.
Option 2: using the U-Bolt bracket supplied with the PTP LPU Kit.
Typical examples of these two configurations are shown in Figure 122 and Figure 123.
NOTE
: Grounding Points are shown unprotected for clarity. Grounding points should be
adequately weatherproofed to prevent corrosion and possible loss of ground continuity.
Figure 122 – Example of PTP-LPU Configuration – Option 1 (Back-to-Back Recommended)