TVF 501 Tests
Star rat Utilization Equipment.
TVF 601 Tests – Revision F
ting ope ions are not applicable to AC
TVF601 Power Failure - One Phase – Rev F
Condition Duration (s)
Run at 400, Repeat at 360, 600 and 800 Hz
A 100 msec 52
B 500 msec 54
C 3 sec 66
D 7 sec 86
TVF 602 Tests – Revision F
TVF601 Power Failure – One, Two Phase – Rev F
Condition Duration (s)
Run at 400, Repeat at 360, 600 and 800 Hz
One Phase
A Phase A, 7 sec - 5x 86
B Phase B, 7 sec - 5x 86
C Phase C, 7 sec - 5x 86
D Phase A, 30 min - 1x 1800
E Phase B, 30 min - 1x 1800
F Phase C, 30 min - 1x 1800
Two Phase
G Phase A&B, 7 sec - 5x 86
H Phase B&C, 7 sec - 5x 86
I Phase A&B, 30 min - 1x 1800
J 1800 Phase B&C, 30 min - 1x
TVF 603 T ts – R es evision F
TVF603 Power Failure – Phase Reversal – Rev F
Condition Duration (s)
Run at 400, Repeat at 360, 600 and 800 Hz
A Phase rotation C-B-A 1800
Phase rotation A-B-C 1800