Instruction manual
9
Systems
POWER CURRENT PER PHASE (IN AMPS)
(At full output
voltage)
VOLTAGE RANGE
MODEL TOTAL PER
PHASE 135 156
(HV1)
270
(HV2)
312
(HV3)
400
(HV4)
FCS-18-3 18KW 6KW 44.4 38.4 22.2 19.2 15.0
FCS-18-1 18KW 18KW 133.2 115.2 66.6 57.6 45.0
FCS-36/2-3 36KW 12KW 88.8 76.9 44.4 38.4 30.0
FCS-36/2-1 36KW 36KW 266.4 230.7 133.2 115.2 90.0
FCS-54/3-3 54KW 18KW 133.2 115.4 66.6 57.6 45.0
FCS-54/3-1 54KW 54KW 399.6 346.2 199.8 173.1 135.0
MECHANICAL
Dimensions 30"w x 36"d plus 4" for J-box x 45"h (18kVA)
Weight 750 lbs (without output transformers) 900 lbs with output
transformers
Air Intake/Exhaust Front/Back
Modularity Output, Controller, Power Supply, Interface
Connectors
-Input Marathon 142 2570
-Output Marathon 142 2570
-Sense Beau 72904
-Interface 3M 3565-100
3M 3564-1001 (mating connector)
Cabinet Casters and forklift
ENVIRONMENTAL, QUALITY, REGULATORY
Operating Temperature 0 to 50°C (derated 300 VA per °C linearly from 35°C to 50°C)
Storage Temperature -40 to +85°C
Operating Altitude 7500 ft.
Humidity 95% RH, non-condensing
E.M.I. CISPR11
Acoustic Noise 65dBA 3 ft., no load