Instruction manual

7
1000-1200 1 ±0.005% 60 Hz
(Limited to 1000 for HV4)
* Phase Angle 0 - 360° 0.5° ±3° B=240 C=120
* Current Limit 0 to Full- 0.5A to +5 to +15% Maximum
Scale 200
Current 5.0A above 200 +5 to +15%
Voltage Stability (24 Hrs) 0.25% FS, 15 minute warm-up
Features
1ø, 3ø operation - user configurable for single cabinet, factory/field configurable by
manufacturer for multi-cabinet systems.
Remote Sense - allows correction for load wiring losses (up to 2% at full load).
Parallel Capability - operate 6 KVA amplifiers in parallel to increase output power
capability.
External Sync Input - causes output signal to track this input in frequency and phase. A
5 volt, 45 to 1200 Hz, 5 milliamp, TTL type signal. Loss of this input forces the output
to the fault mode.
Indicators - Power On
Module Failure
Overtemp
Output Fault
Status Reporting
Field Power Upgrades (by manufacturer) - cabinets may be added up to three total in a
system; two or three cabinet systems may be converted 1ø to 3ø or 3ø to 1ø.
Ramp/Sweep of Voltage, Frequency, Phase and Current Limit up to 2 functions
simultaneously.
Storage Registers - store up to 16 setups.
Calibration - perform either via front panel keypad or IEEE488 bus.