Wiring Guide

9
Sequence of Operation / Settings
A demand occurs and closes RW (TT)
Relay #1 and relay #2 both fire connecting the
common terminal to the NO terminal.
If the factory installed jumper has not been
removed, the NO terminal of relay #1 will
deliver the hot leg of 120 VAC. Relay #2 has
dry contacts.
The zone LED illuminates.
The demand is satisfied and opens RW (TT).
The relay contacts return to their normal
position (common to normally closed).
The zone LED turns off.
Description of terminals
= Ground
N = Neutral (Common leg of 120 VAC)
L = Line (live leg of 120 VAC)
C = Common terminal
NO = Normally Open terminal
NC = Normally Closed terminal
Note: There is a factory installed jumper between the 120
VAC line (L) and the common terminal of relay #1 (C).
Thermostat terminals
R = 24 VAC
W = Heat call
C
= Common of 24 VAC
WARNING: NEVER CONNECT R & C DIRECTLY,
this will be a direct short on the 24 VAC supply