Instructions
2-way installed on the supply
Flow Characteristics
Connection size Flow Coefficient
Max. Close-off P
1/2" 1.0 Cv (0.9 kv) 75 PSI (517 kPa)
1/2"
2.5 Cv (2.2 kv) 50 PSI (345 kPa)
3/4"
1/2"
3.5 Cv (3.0 kv) 30 PSI (207 kPa)
3/4"
3/4"
5.0 Cv (4.3 kv) 25 PSI (172 kPa)
1"
3/4"
7.5 Cv (6.5 kv) 20 PSI (138 kPa)
1"
1"
7.5 Cv (6.5 kv) 20 PSI (138 kPa)
1 1/4"
Installation
The valve can be installed vertically or horizontally, but not turned upside down.
- A 3-way valve cannot be transformed into a 2-way valve and vice versa.
- The flow is from A to B (see diagram below) and must be installed so the paddle
closes against the direction of flow as indicated in the following diagrams.
- The 2-way valves can be installed on the
supply or on the return; for correct
installation it is necessary to respect the
direction of flow indicated from the arrow
on the body valve.
2-way valve with normally closed actuator
2-way installed on the return
A
B